I&O Manual

DEKA DURATION DD5300
72
3.4 High Voltage Module Configuration
ATTENTION: The High Voltage mode mandates that the Battery Modules must be connected in series.
ATTENTION: The following table provides the possible module configurations. NO OTHER
configurations are suitable.
ATTENTION: Before connecting an HV inverter with the HV BOX terminal, always check the
Inverter Input range.
``
DD21002 HV Box
Tower -1
Min Vdc
Max Vdc
Capacity kWh
Modules
in
Series
4
200
233.6
20.8
5
250
292
26
6
300
350.4
31.2
7
350
408.8
36.4
8
400
467.2
41.6
Tower -2
Min Vdc
Max Vdc
Capacity kWh
Modules
in
Series
9
450
525.6
46.8
10
500
584
52
11
550
642.4
57.2
12
600
700.8
62.4
13
650
759.2
67.6
14
700
817.6
72.8
15
750
876
78
16
800
934
83.2
ATTENTION
For the calculation of the energy of a cluster (in both LV and HV systems) the nominal capacity of a battery is
generally counted in 5.3kWh as a result of the multiple connection inefficiency, estimated at a loss of 2%.