I&O Manual

DEKA DURATION DD5300
85
3.7.1 LED Visual Indication Lights
RUN Button
Each Battery Module has its own RUN button, however, when used with the HV Box during normal operation, the RUN
button has no function and is bypassed by the control communications from the HV Box.
Caution: In the HV configuration, the RUN button will have no effect on the operation of the Battery Module and
the operator should not assume that the RUN button will have switched off the Battery Module when pressed.
3.7.1.1 Power Switch + Run Button
The Power Switch and the Run Button are located to the right of the battery terminal connections on the side of the Battery
Module.
The RUN Button is a GREEN LED button and will provide the user with the following indications depending on the state of the
battery.
STARTUP: Turn ON the Power Switch (1 = ON 0= OFF)
A 2-second press on the RUN Button will turn the Battery Module on.
During the startup procedure, the RUN button will blink until the safety inspection has been completed by the BMS.
SHUTDOWN: A 5-second press and hold on the RUN Button will turn the Battery Module off.
Turn OFF the Power Switch (1 = ON 0= OFF)
Other functions of the RUN Button are explained in the relevant sections of this manual.
Attention: Read this entire manual thoroughly to understand the correct startup and shutdown procedures for
each battery configuration.
Attention: Illustrations shown are for reference only. Please always refer to the physical Battery Module in front
of you, and if the module has a different configuration to this manual, stop all activity immediately and contact your
Deka Duration technical representative.
3.7.2 Stand-Alone Battery Front Panel Control * FORCED CHARGE*
3.7.2.1 Start Battery
Press the Power Button of the HV Box for 3 or more seconds (depends on the system status).
The GREEN RUN light should come on. The HV Box module has been activated normally and the Battery Modules should come
on automatically. If they do not, press the RUN Button of each module and wait for the HV Box string diagnosis. If the HV Box
shows a warning LED light (RED), turn the string OFF and connect the PC software for debugging.
3.7.2.2 Shut Down Batteries and HV Box
Long press the RUN Button on the battery module for five seconds and the Run Button on the HV Box.
The GREEN RUN light should go off. The HV Box has been shut down normally.
By switching off the HV Box, all the Battery Modules should turn off automatically. If they do not turn off automatically, shut
down manually by pressing and holding the Run Button on the battery module for 5 seconds.
Always completely shut down the system when performing a mechanical inspection.