Manual

M.K.Plastics Corp. Montréal, Québec www.mkplastics.com
11
STEP-DOWN TRANSFORMER
(208/230/460/575V - 1 PHASE)
(24V OR 120V - 1 PHASE)
BYPASS DAMPER ACTUATOR
(BY OTHERS)
HIGH VOLTAGE
LOW VOLTAGE
STEP-DOWN TRANSFORMER
(208/230/460/575V - 1 PHASE)
(24V OR 120V - 1 PHASE)
BYPASS DAMPER ACTUATOR
(BY OTHERS)
HIGH VOLTAGE
LOW VOLTAGE
STEP-DOWN TRANSFORMER
(208/230/460/575V - 1 PHASE)
(24V OR 120V - 1 PHASE)
BYPASS DAMPER ACTUATOR
(BY OTHERS)
HIGH VOLTAGE
LOW VOLTAGE
STEP-DOWN TRANSFORMER
(208/230/460/575V - 1 PHASE)
(24V OR 120V - 1 PHASE)
BYPASS DAMPER ACTUATOR
(BY OTHERS)
HIGH VOLTAGE
LOW VOLTAGE
Figure-7. Bypass Damper Wiring Schematic
Operation Checklist
Verify that proper safety precautions have been followed.
Electrical power must be locked off.
Check fan mechanism components:
Nuts, bolts, set screws are tight.
Mounting connections are properly made and tightened.
Bearings are properly lubricated.
Wheel, drives and fan surfaces are clean and tightened.
Rotating assembly turns freely and does not rub.
Drives on correct shafts, properly aligned, and properly tensioned.
Check fan electrical components:
Motor is wired for proper supply voltage.
Motor was properly sized for power of rotating assembly.
Motor is properly grounded.
All leads are properly insulated.
Trial “bump”:
Turn on power just long enough to start assembly rotating.
Check rotation for agreement with rotation arrow.
Listen for any unusual noise.
Run unit up to speed:
Bearing temperatures are acceptable (<200°F) after one to two hours of operation.
Check for excess levels of vibration. Filter in readings should be 0.15 inches per second or less.
After one week of operation:
Check all nuts, bolts and setscrews and tighten if necessary.
Readjust drive tension if necessary.