User Manual
Storage 
If the fan is stored for any length of time prior to installatio n, completely coat the bearings, (if the fan has pillow-block bearings), 
with grease or moisture inhibiting oil (refer to Lubricants on page 8). Rotate the wheel several revolutions every three to five 
days to keep a coating of grease on all internal bearing parts. 
Outdoor Storage 
 To maintain good working condition of the fan when it is stored outdoors, follow the additional instructions below. 
1.  Cover the outlet to prevent the accumulation of dirt and moisture in the housing. 
2.  Periodically rotate the wheel and operate dampers (if supplied). 
3.  Periodically inspect the unit to prevent damaging conditions. 
Personal Safety 
Disconnect switches are recommended. Place the disconnect 
switch near the fan in order that the power can be swiftly cut 
off in case of an emergency, and in order that maintenance 
personnel are provided complete control of the power source. 
Fan Installation 
Roof Mounted Fans 
Roof mounted fans should no rmally be attac hed to equ ipment sup port cur bs to keep them above th e roof line b y at least 12”. To 
install the roof curb, the fan must be disassembled to be able to attach the fan to the curb. See Fig. 2 for details. 
Fig. 2 – Roof Curb Mounted 
2