Safety Instructions

Installation
15
Connecting to Secure I/O 2
Secure I/O 2 is an I/O device, can be connected to AE-M with the RS-485 cable. Security can be maintained even if the connection
between AE-M and Secure I/O 2 has been lost or the power supply to AE-M has been shut off due to external factors.
Use the RS-485 cable with AWG24, twisted pair, and less than 1.2 km in length.
If connecting with a RS-485 daisy chain, connect the termination resistor (120 Ω) to both ends of the daisy chain connection. If
connected to the middle line, the signal level becomes smaller and the communication performance will deteriorate. Make
sure to connect it to both ends of the daisy chain connection.
AE-M
PC
Secure I/O 2
Hub
Door button
Door sensor
Power
RS-485 connection
1 - 485 TRXP Blue (White stripe)
2 - 485 TRXN Yellow (Black stripe)
3 - 485 GND White (Black stripe)
22
1
Door lock
DC
power
DC
power
DC
power
21
3
Power supply connection
21 - PWR +VDC Red
22 - PWR GND Black (White stripe)
RS-485
2