Service manual

WARNING
1. Improper installation, adjustment, alteration, service or
maintenance can cause property damage, injury or
death, and could cause exposure to substances which
have been determined by various state agencies to
cause cancer, birth defects, or other reproductive harm.
Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
2. The installation and maintenance instructions in the unit
manual as well as the following instructions must be
followed to provide safe, efficient and trouble-free
operation. In addition, particular care must be exercised
regarding the special precautions listed on page 2 of the
units Installation and Service Manual. Failure to properly
address these critical areas could result in property
damage or loss, personal injury, or death. These
instructions are subject to any more restrictive local or
national codes.
6-530.13
55HH7733775566AA11 ((RReevv.. CC))
JJaannuuaarryy,, 22000022
IINNSSTTAALLLLAATTIIOONN IINNSSTTRRUUCCTTIIOONNSS
DDIIMMEENNSSIIOONNSS AANNDD SSUUBBMMIITTTTAALL DDAATTAA
ppoowweerr eexxhhaauusstt aacccceessssoorryy
ffoorr ggrraavviittyy vveenntteedd ggaass--ffiirreedd eeqquuiippmmeenntt
CAUTION
This power exhauster (for horizontal or vertical venting) is
designed for use on gas-fired unit heaters and duct furnaces
made by Modine Manufacturing Company. The power
exhauster adapter is to be used with the power exhauster.
Do not use the adapter on any heater model other than that
specified in this manual. A restrictive type vent cap (i.e.
Breidert Type L, Gary Steel 1092) should be used when
power exhausting.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
PPaacckkaaggiinngg
The power exhauster is shipped in two packages. The power
exhaust in one carton and the adapter kit for the unit heater or
duct furnace in a separate carton.
AApppplliiccaattiioonn
WWhheenn ttoo uussee tthhiiss PPoowweerr EExxhhaauusstt
To overcome venting difficulties of gas-fired unit heaters and
duct furnaces due to:
1. Non-linear or irregular vent runs.
2. Long horizontal vent runs.
3. Negative pressure areas.
4. Low ambient temperature areas restraining natural drafts.
AAvvaaiillaabbllee VVoollttaaggeess
The PV-124 power exhaust is furnished with tri-voltage
115V/208V-230V single phase motors. Each motor displays a
wiring diagram showing the wiring schematic for 115 V or
208V/230V power. When utilizing 460V 3ø power, a 250VA
transformer must be used to step down to 230V or 115V. The
power exhaust includes a 25-volt factory mounted relay for
operation with the gas unit’s 25-volt control system.
OOppeerraattiioonn
The power exhaust contains an integrally mounted motor that is
controlled by a room thermostat. When the thermostat senses
the requirement for heat, it starts the exhaust motor. When the
motor reaches proper running speed, a built-in centrifugal switch
closes; thus the automatic gas valve, which is electrically in
series with the switch, becomes energized and gas flows to the
burner. When the thermostat is satisfied, the exhaust motor
stops, centrifugal switch opens, and gas valve closes. If the
motor does not run or reach proper running speed, the
centrifugal switch will not close and the automatic gas valve will
not be energized.
IMPORTANT
The use of this manual is specifically intended for a qualified
installation and service agency. All installation and service of
these units must be performed by a qualified installation and
service agency. Modine manuals may contain excerpts from
component supplier literature adapted for Modine products.
Any accompanying component supplier literature is for
general information.