Installation and Service Manual

September, 2006
INSTALLATION
Step Down Transformer Kit
models HSB/HC, V/VN, PT/PTN, WTC/WSC, WVC/WVN, WPC/WPN
manufactured after September 1, 2005
Special Precautions
1) Installation of wiring must conform with local building
codes, or in the absence of local codes, the National
Electric Code ANSI/NFPA 70 - Latest Edition. Unit must
be electrically grounded in conformance to this code. In
Canada, wiring must comply with CSA C22.1, Part 1,
Electrical Code.
2) Disconnect supply voltage.
3) Verify electrical system supply voltage to ensure it matches
the accessory transformer primary voltage rating.
4) Verify that the unit heater supply voltage listed on the
serial plate is 115 Volts, 60 Hertz, 1 Phase.
5) Verify that the accessory transformer is correctly sized for
the unit type, size, and supply voltage. The accessory item
codes and kVA sizes are shown in Table 1.1.
Table 1.1
Transformer Accessory Item Codes and Ratings
1-556.2
5H79544A1 Rev. B
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
Warning
1) Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
2) All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a hazard
to persons and property.
3) Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4) Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
caution
Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% less than the rated
voltage.
important
The use of this manual is specifically intended for a qualified
installation and service agency. All installation and service
of these units must be performed by a qualified installation
and service agency. These manuals may contain excerpts
from component supplier literature adapted for Modine
products. Any accompanying component supplier literature
is for general information.
Supply Voltage
200V/60Hz/ 230/460V/ 575V/60Hz/
1 or 3 phase 60Hz/3 phase 3 phase
Item Item Item
Model Size Code kVA Code kVA Code kVA
HSB/HC 18-63 48094 0.50 48099 0.25 48108 0.25
HSB/HC 86-121 48100 0.50 48109 0.50
HSB/HC 165-193 48095 1.00 48101 0.75 48110 0.75
HSB/HC 258-340 48102 1.00 48111 1.00
V/VN 42-59 48096 0.50 48103 0.25 48112 0.25
V/VN 78-139 48104 0.50 48113 0.50
V/VN 161-212 48097 1.00 48105 0.75 48114 0.75
V/VN 247-333 48106 1.00 48115 1.00
PT/PTN 279-333 48098 1.00 48107 1.00 48116 1.00
HSB/HC,
WTC/WSC
48094 0.50
48095 1.00
48096 0.50
48097 1.00
V/VN,
WVC/WVN
PT/PTN,
WPC/WPN

Summary of content (4 pages)