User Manual
20
6-189.14
PERFORMANCE DATA - HOODS FOR PROPELLER MODELS
Table 20.1 - Downtown Hood General Performance Data for HD/PDP/PTP (feet)
H
S
S
Figure 20.1 - 30°, 60°, and 90° Downward Deflector Hoods
MOUNTING
HEIGHT
X
Y
Y
Z
Z
X
60 DOWNTURN
30  DOWNTU RN
Note:
X = Feet from  H eater to Start of Floor C overage
Y = Feet to End of Floor C overage
Z = Feet to End of Throw
60 
30 
30  DOWNTU RN
60  DOWNTU RN
30° HOOD 60° HOOD
90° HOOD
Figure 20.2 - 30° and 60° Throw/Floor Coverage 
Figure 20.3 - 90° Hood Throw/Floor Coverage 
Model HD Sizes Model PDP Sizes Model PTP SIzes
60 75 100 125 150 175 200 250 300 350 400 150 175 200 250 300 350 400
Max. Mtg. Height (ft.)
9 11 11 12 18 18 18 22 24 24 24 16 16 15 20 22 21 23
30° Hood
X
4 5 5 6 6 9 6 8 8 8 8 6 6 7 7 8 7 11
Y
11 14 14 16 20 26 18 24 26 24 24 20 17 20 22 25 23 31
Z
16 21 20 23 29 37 26 35 38 36 35 29 26 29 32 37 34 44
60° Hood
X
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Y
8 12 12 14 13 23 12 16 19 16 16 17 14 17 18 21 18 26
Z
12 17 17 19 19 32 17 23 28 24 23 24 21 24 26 30 26 37
90° Hood
S
10 14 13 15 23 25 22 29 32 20 29 17 16 16 20 22 21 24