User Manual

10
6-189.14
BLOWER PERFORMANCE DATA - MODEL BTP
Table 10.1 - Power Code Description - Blower Model BTP j
j For selection of correct Power Code, refer to the Tables on pages 11-12.
Table 10.2 - Filter Static Pressure Drop k
BTP150 BTP175 BTP200 BTP250 BTP300 BTP350 BTP400
Filter Static (“W.C.) 0.1 0.2 0.1 0.2 0.2 0.2 0.2
k For blower units with enclosure and filter, add the following static pressures to the static pressure determined by the system designer for total
external static pressure.
BTP150 BTP175 BTPS250 BTP300 BTP350 BTP400
Power
Code Voltage Phase HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
01 115 1 1/4 230 - - - - - - - - - -
02 115/230 1 1/3 230 1/3 238 1/2 204 1 240 1 1/2 250 1 1/2 247
08 208-230/460 3 1/3 230 1/3 238 1/2 204 1 257 1 1/2 251 1 1/2 248
11 575 3 1/3 231 1/3 239 1/2 204 1 257 1 1/2 251 1 1/2 248
13 115/230 1 1/3 232 1/2 229 1 241 1 241 1 1/2 247 - -
19 208-230/460 3 1/3 232 1/2 229 1 258 1 258 1 1/2 248 2 177
22 575 3 1/3 233 1/2 229 1 258 1 258 1 1/2 248 2 177
24 115/230 1 1/2 229 1 175 1.5 23 1 1/2 243 1 1/2 252 - -
30 208-230/460 3 1/2 229 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
33 575 3 1/2 229 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
35 115/230 1 1 175 1 1/2 237 - - 1 1/2 23 - - - -
41 208-230/460 3 1 253 1 1/2 234 2 180 1 1/2 177 2 177 5 245
44 575 3 1 253 1 1/2 234 2 180 1 1/2 177 2 177 5 245
52 208-230/460 3 - - - - - - 2 177 2 180 - -
55 575 3 - - - - - - 2 177 2 180 - -
63 208-230/460 3 - - - - - - 3 112 3 246 - -
66 575 3 - - - - - - 3 112 3 246 - -
74 208-230/460 3 - - - - - - - - 5 245 - -
77 575 3 - - - - - - - - 5 245 - -