User Manual

24
6-189.14
Selection Example Conditions (Blower Unit)
In the following example, select a unit heater to meet the
following conditions:
1. Heating output capacity = 156,000 Btu/Hr per design engineer
2. External Static Pressure = 0.2.
3. Internal Static Pressure = 0.0. No static producing accessories
are required
4. Heat exchanger and burner = Aluminized Steel
5. Gas Type = Propane
6. Gas Controls = Two stage Intermittent Pilot
7. Supply Voltage: 230V/60Hz/3Ph
8. Altitude: 1,000 feet
9. CFM = 2,400
Selection Example Solution (Blower Unit)
With the information listed above, the basic model, using the
information in this catalog and the Model Nomenclature shown on
page 32, can be selected as shown in the following example:
1. Determine the Model and Input Rating (MBH):
Using the Heating output capacity, the Furnace Input Rating is
determined from Table 13.1 The closest model to 156,000 Btu/Hr
output has an Btu/Hr Input rating of 200,000 Btu/Hr so the
Furnace Input Rating = 200. The corresponding model for a 200
size, blower, power vented unit heater is BDP. The model and
size are a BDP200.
2. Determination of Heat Exchanger/Burner/Drip Pan Material:
From item #4 in the example, the Heat Exchanger and
Burner required are aluminized steel. Thus, the Heat Exchanger
Material = A from the Model Nomenclature on page 32.
3. Determine the development sequence:
From item #6 in the example, the IPI results in the Development
Sequence = E from the Model Nomenclature on page 32.
4. Determine Power Code Required:
From page 16 we see that a unit requiring a static of 0.2 and a
cfm of 2400 requires a 1/3 horsepower motor with a -102 drive
that is turned open 4.0 turns. Referring to Table 11.1 it can be
determined that for a BDP200 with a 1/3 HP motor and a -102
drive operating on 230V/60Hz/3Ph that if will have a power
code = 24.
5. Determine the control type:
From item #5 in the example, the gas type is Propane Gas and
controls are Two Stage. Given the supply voltage listed in #7, we
can refer to Tables 18.1 and 18.2 to determine what controls are
needed. This results in a Control Code (CC) = 88.
At this point we have a full model number of:
BDP200AE2488NBAN
6. Altitude:
Since deration of gas fired unit heaters is only required for
units to be installed at 2,000 ft or greater, no high altitude kit is
required.
UNIT SELECTION