Brochure

C
US
4
75-136.49
Request Catalog 6-189 For Complete Technical Information and Specifications.
TAPE OUT
GAS-FIRED, POWER-EXHAUSTED
MODEL HD
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
MODEL PDP
MODEL PTP
For applications requiring a low profile unit, Modine offers the Hot Dawg
®
unit heater. The Hot Dawg
®
may be installed in residential or commercial applications just one inch below the ceiling. The
superior quality matched with the following features makes the Hot Dawg
®
unit heater an easy
choice for a variety of applications:
82% thermal efficiency for fuel savings.
Uses natural or propane gas (field convertible from natural to propane gas).
Certified for residential, commercial and industrial use.
Lightweight, easily installs 1" from ceiling with only two angle brackets (standard on 30-75,
accessory for 100-125).
Install quickly and easily with knockouts for quick access to gas and electricity.
The standard power exhauster allows the unit to be vented vertically or horizontally and is
designed to use the smallest diameter vent pipe possible.
Permanently-lubricated motor for trouble-free dependability.
Full 10-year warranty on heat exchanger.
Available in both propeller fan and centrifugal blower configurations.
The PDP (propeller) power vented gas-fired unit heater is a product that is inexpensive to install,
easy to use, and offers excellent in-service economy. The PDP model series expands on the size
range of the HD model series providing product that is certified for commercial and industrial
applications in sizes from 150 through 400MBH.
For blower model data, see page 8.
The PTP features a stainless steel tubular heat exchanger as STANDARD on all units with a
10-year heat exchanger warranty, providing customers with a peace of mind. Users of the PTP will
also benefit from a design that allows quick and easy installations.
Table 4.1 - Propeller Unit Model HD and PDP General Performance Data
Model HD Sizes Model PDP Sizes
30 45 60 75 100 125 150 175 200 250 300 350 400
Btu/Hr Input
30,000 45,000 60,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr Ouput
24,600 36,900 49,200 61,500 82,000 102,500 123,000 143,500 164,000 205,000 246,000 287,000 328,000
Entering Airflow (CFM)
@ 70°F
505 720 990 1160 1490 1980 2180 2550 2870 3700 4460 4870 5440
Air Temp. Rise (°F) 44 46 45 48 50 47 51 51 52 50 50 53 54
Max. Mounting
Height (Ft.)
10 10 12 14 12 16 16 17 15 19 21 20 19
Heat Throw (Ft.) @
Max Mtg Ht
25 27 36 38 42 56 55 59 51 67 74 70 69
82% Thermal Efciency • Horizontal or Vertical Venting Field Convertible to Propane 100% Shut-Off with
Continuous Retry Commercial or Residential Applications
Table 4.2 - Propeller Unit Model PTP General Performance Data
Ratings shown are for elevations up to 2,000 Ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4%
for each 1,000 feet above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from
bottom of unit, and without deflector hoods. For units equipped with deflector hoods.
Model PTP Sizes
150 175 200 250 300 350 400
Btu/Hr Input
150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr Ouput
123,000 143,500 164,000 205,000 246,000 287,000 328,000
Entering Airflow (CFM) @ 70°F
2140 2725 2870 3995 4545 5280 5995
Air Temp. Rise (°F)
53 48 52 47 50 50 51
Max. Mounting
Height (Ft.)
15 14 15 18 19 18 21
Heat Throw (Ft.) (@
Max Mtg Ht)
51 50 53 62 69 65 74