Wiring Guide

1-454.10
September, 2006
WIRING DIAGRAMS
steam/hot water unit heaters
Models HSB/HC, V/VN, PT/PTN, WTC/WSC, WPC/WPN, WVC/WVN
Diagram Selection
Diagrams are provided for both single and three-phase circuits,
and are readily identified in the Selection Table 1.1.
Select the correct wiring diagram as follows:
1. Determine unit heater model, size and voltage/power code.
2. Review Table 1.1 to locate the page number that matches
the characterstics of the heater from step 1.
Example Selection
Select the wiring diagram for an HSB340 for use on
460V/60 hz/3 phase supply voltage.
In Table 1.1 select the page number where the column for the
voltage intersects with the row for HSB340. The correct wiring
diagram for this unit is found on page 2. Note that footnote
indicates that the unit will be Power Code 01, 115V/60Hz/1ph
requiring an accessory transformer. See literature #1-556 for
additional details.
Two-in-one Diagrams
Two wiring diagrams are furnished for each circuit configuration
in this manual. Included are a connection diagram at the left
for field installation and circuit schematic at the right to aid in
continuity and trouble shooting.
The heavier lines in the connection diagram indicate line voltage;
the lighter lines indicate low voltage. Solid lines show pre-wiring
performed at the factory; dotted lines inform the installer of
connections required to put the heater in operation.
NOTE: As indicated in every diagram, all wiring must comply
with the National Electrical Code and all local codes. All
components must agree with their respective power source.
CAUTION
Turn off all power and gas to unit before wiring. Failure to wire
this unit according to this wiring diagram may result in injury
to the installer or user. For deviations, contact factory.
Motor Voltage and Power Code
115/60/1 200/601 230/60/1 200-208/60/3 230/460/60/3 575/60/3
01 - 02 04 05 10
Model Page Page Page Page Page Page
HSB/HC, WTC/WSC 18-340 2 2 2 2  2  2 
V/VN, WVC/WVN 42-279 2 2 2 2  2  2 
V/VN, PT/PTN, WVC/WVN, WPC/WPN 333 3 3 3 3  3  3 
V/VN, PT/PTN, WVC/WVN, WPC/WPN 385-952 - - - 4 4 4
Table 1.1
Wiring Diagram Page Location for Units with Totally Enclosed Motors
➀ For supply voltages of 200V/60Hz/1ph and all non-explosion proof 3 phase voltages of 200, 230, 460 and 575, Model Numbers indicated with Note , require that
a 115V/60Hz/1 phase Power Code 01 unit heater be used with a shipped loose accessory transformer. See literature #1-556 for additional information.
VN/PTN, WVN/WPN952 not available.
For HSB/HC, WTC/WSC (all sizes) and VN/PTN, WVN/WPN (sizes 333 and below) with Power Code 04, 05 and 10 manufactured before September, 2005, use
the wiring diagram on page 4.