Install Instructions
6-583.4
3
BEFORE YOU BEGIN
In the U.S., the installation of these units must comply with the 
National Fuel Gas Code, ANSI Z223.1 - latest edition (also 
known as NFPA 54) and other applicable local building codes. 
In Canada, the installation of these units must comply with local 
plumbing or waste water codes and other applicable codes and 
with the current code CSA-B149.1. 
1.  All installation and service of these units must be    
  performed by a qualified installation and service agency   
  only as defined in ANSI Z223.1 (NFPA 54) - latest edition,  
  or in Canada by a licensed gas fitter. 
2.  This unit is certified with the controls furnished. For   
  replacements parts, please order according to the   
  replacement parts list on serial plate. Always know your   
  model and serial numbers. Modine reserves the right to   
  substitute other authorized controls as replacements.
3.  Unit is balanced for correct performance. Do not alter fan   
  or operate motors at reduced speed.
4.  Information on controls is supplied separately.
5.  The same burner is used for natural and propane gas.
SPECIAL PRECAUTIONS / SI (METRIC) CONVERSION FACTORS 
  cAUTION
1.  All literature shipped with this unit should be kept for future  
  use for servicing or service diagnostics. Leave manual with  
  the owner. Do not discard any literature shipped with this unit.
2.  Consult piping, electrical, and venting instructions in this   
  manual before final installation. 
3.  Do not attach ductwork, air filters, or polytubes to any   
  propeller unit heater.
  cAUTION
17. When leak testing the gas supply piping system, the   
  appliance and its combination gas control must be isolated 
  during any pressure testing in excess of 14" W.C. (1/2 psi).
18. The unit should be isolated from the gas supply piping 
  system by closing its field installed manual shut-off valve. 
  This manual shut-off valve should be located within 6' of 
  the heater.
19. Turn off all gas before installing appliance.
20. Ensure that the supply voltage to the appliance, as 
  indicated on the serial plate, is less than 5% below the   
  rated voltage.
21. Check the gas inlet pressure at the unit upstream of the   
  combination gas control. The inlet pressure should be 6-7" 
  W.C. on natural gas or 12-14" W.C. on propane. If inlet 
  pressure is too high, install an additional pressure 
  regulator upstream of the combination gas control.
22. Service or repair of this equipment must be performed   
by a qualified service agency.
23. Do not attempt to reuse any mechanical or electronic 
  ignition controllers which has been wet. Replace defective  
  controller.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate 
ANY gas-fired appliances in areas where corrosive vapors 
(i.e. chlorinated, halogenated, or acidic) are present in the  
atmosphere.
2. To prevent premature heat exchanger failure, the input to   
the appliance as indicated on the serial plate must not   
exceed the rated input by more than 5%.
3. To check most of the Possible Remedies in the trouble- 
shooting guide listed in Table 17.1 refer to the applicable 
sections of the manual.
  To Convert  Multiply By  To Obtain
  "W.C.  0.249  kPa 
  °F  (°F-32) x 5/9  °C 
  Btu  1.06  kJ
  Btu/ft
3
  37.3  kJ/m
3
  Btu/hr  0.000293  kW
  CFH (ft
3
/hr)  0.000472  m
3
/min 
  CFH (ft
3
/hr)  0.00000787  m
3
/s
 CFM (ft
3
/min)  0.0283  m
3
/min 
 CFM (ft
3
/min)  0.000472  m
3
/s
 To Convert  Multiply By  To Obtain
  feet  0.305  m
  Gal/Hr.  0.00379   m
3
/hr 
  Gal/Hr.  3.79  l/hr
  gallons  3.79  l
 Horsepower  746  W
  inches  25.4  mm 
  pound  0.454  kg 
  psig  6.89  kPa 
  psig  27.7  "W.C.
SI (METRIC) CONVERSION FACTORS