Product Troubleshooting

CALL FOR HEAT UNIT DOES NOTHING
Green Light on Control Board is OFF. 24 VAC NOT
present between Sec & Com on board
Possible Causes
Check for loose connections
Check incoming power (115 VAC)
If incoming power is correct, check for 24VAC at
the secondary of the transformer. If incoming
voltage is correct and no voltage at the secondary,
replace transformer