Product Troubleshooting

CALL FOR HEAT UNIT DOES NOTHING
Green Light on Control Board is OFF 24 VAC IS
present between Sec & Com on board
Possible Causes
-Check fuse for blown element.
Remove the fuse. Check for continuity.
Do NOT just inspect element. Check for
continuity. If the fuse is bad, replace fuse.
-Check for loose connections
-If fuse is not blown, terminal board is not letting
24 VAC through the board. Replace board.