Product Troubleshooting

ONE FLASH NO POWER EXHAUSTER
Pressure switch does not close within 30 seconds of inducer energized
Unit sequence:
Green Light on, call for heat, 24 volts at R & W on
board. Nothing happens. Green light will give One
flash. Fan motor will not cycle on.
Possible cause:
Defective exhauster motor. Receiving 115 volts from
IND and NEUTRAL terminals on board, but will not
run. Replace exhauster.
Defective board. Not sending 115 volts from IND and
NEUTRAL terminals to exhauster. Replace board