Product Troubleshooting

TWO FLASHES - TROUBLESHOOTING CODES
Pressure switch is closed before inducer is energized
Unit Sequence: Green light on, call for heat, 24 volts
at R & W terminal. Nothing will happen to unit
operation except Green Light will give Two Flashes.
Possible Cause:
Defective or damaged pressure switch
Showing continuity between terminals in non-heat
mode
The two yellow wires are showing continuity in non-
heat mode.
Defective board (verify and replace if bad)