Product Troubleshooting
Table Of Contents
- Troubleshooting HD Direct Spark Units
- How to use this application
- Table of contents
- Definitions & Basic Operation
- Flame Status - Yellow LED labeled “FLAME”
- Heating Sequence of operation
- End of Heating Sequence of operation
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Troubleshooting flash codes
- Troubleshooting flash codes
- No flashes – Troubleshooting codes
- One Flash - Troubleshooting codes
- One Flash – No Power Exhauster
- One Flash – Pressure switch Won’t close
- Two flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Five Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Seven Flashes - Troubleshooting codes
- Before REPLACING THE CONTROL BOARD
- For additional help Installation & Service manual live operators
- Slide Number 41
TWO FLASHES - TROUBLESHOOTING CODES
• Pressure switch is closed before inducer is energized
• Unit Sequence: Green light on, call for heat, 24 volts
at R & W terminal. Nothing will happen to unit
operation except Green Light will give Two Flashes.
• Possible Cause:
• Defective or damaged pressure switch
• Showing continuity between terminals in non-heat
mode
• The two yellow wires are showing continuity in non-
heat mode.
• Defective board (verify and replace if bad)