Product Troubleshooting
Table Of Contents
- Troubleshooting HD Direct Spark Units
- How to use this application
- Table of contents
- Definitions & Basic Operation
- Flame Status - Yellow LED labeled “FLAME”
- Heating Sequence of operation
- End of Heating Sequence of operation
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Troubleshooting flash codes
- Troubleshooting flash codes
- No flashes – Troubleshooting codes
- One Flash - Troubleshooting codes
- One Flash – No Power Exhauster
- One Flash – Pressure switch Won’t close
- Two flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Five Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Seven Flashes - Troubleshooting codes
- Before REPLACING THE CONTROL BOARD
- For additional help Installation & Service manual live operators
- Slide Number 41
THREE FLASHES - TROUBLESHOOTING CODES
• Open in the safety switch circuit (limit switch or flame roll out
switch is open)
• The limit switch is ignored unless a call for heat is present (R to
W energized). If the limit switch is open and a call for heat is
present, the control de-energizes the gas valve, runs the blower
motor, and runs the power exhauster. The control will flash “3”
on the LED until the limit switch closes. When the switch re-
closes or the call for heat is lost, the control runs the power
exhauster through post-purge and runs the blower through the
fan off delay. The control will return to normal operation after the
blower off delay is completed.
• Possible Causes