Product Troubleshooting

SIX FLASHES - TROUBLESHOOTING CODES
Open in the safety switch circuit (limit switch or flame
roll out switch is open). Main air mover CYCLES ON.
Unit sequence:
Green Light on, call for heat. Power exhauster cycles on.
Fan Motor Cycles on. Green light starts six flashes.
Possible cause:
Open contacts due to over-firing of unit (flame roll out switches
some and some limit switches are manual reset).
Check gas pressure. Check to make sure nothing is blocking airflow
out of unit.
Wire off limit or flame rollout switch. Limit or flame rollout switch
shorting to unit. Defective limit or flame rollout switch.
Defective board, not letting 24 VAC through limits.