Product Troubleshooting
Table Of Contents
- Troubleshooting HD Direct Spark Units
- How to use this application
- Table of contents
- Definitions & Basic Operation
- Flame Status - Yellow LED labeled “FLAME”
- Heating Sequence of operation
- End of Heating Sequence of operation
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Troubleshooting flash codes
- Troubleshooting flash codes
- No flashes – Troubleshooting codes
- One Flash - Troubleshooting codes
- One Flash – No Power Exhauster
- One Flash – Pressure switch Won’t close
- Two flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Five Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Seven Flashes - Troubleshooting codes
- Before REPLACING THE CONTROL BOARD
- For additional help Installation & Service manual live operators
- Slide Number 41
FLAME STATUS - YELLOW LED LABELED “FLAME”
• Flame Status LED is Lit - When flame is sensed, the
flame LED is lit.
• Flame LED flashes slowly - Flame current is below
1.0 uA (+/-50%), the to indicate “weak” flame.
Back Start Over
• Flame LED flashes fast - Flame is present with
gas valve off. If flame is sensed longer than 4
secs while the gas valve is de-energized, the
control shall energize the power exhauster
and indoor blower motor. When flame is no
longer sensed, the power exhauster will run
through post-purge and the blower motor will
run through fan off delay time. The control
will do a soft lockout, but will still respond to
open limit and flame. The Flame LED shall
flash rapidly when lockout is due to undesired
flame.
Yellow Flame LED