Instructions / Assembly

15
6-583.8
Supply
Voltage
Power Code
Model HD Sizes Model HDB Sizes
30 45 60 75 100 125 60 75 100 125
115V
1 Phase
01 (115V)
Motor Amps 2.40 2.40 1.95 1.95 2.50 2.20 5.70 7.10 9.50 9.50
Total Amps 3.70 3.70 3.75 3.75 5.05 4.75 7.50 8.90 12.05 12.05
Transformer kVA n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
208V
1 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 1.00 1.00 1.00 1.50 1.50 1.50
208V Total Amps 2.05 2.05 2.07 2.07 2.79 2.63 4.15 4.92 6.66 6.66
230V
1 Phase
01 (115V) with
Transformer
Transformer kVA 0.5 0.5 0.5 0.5 0.75 0.75 1.00 1.50 1.50 1.50
230V Total Amps 1.85 1.85 1.88 1.88 2.53 2.38 3.75 4.45 6.03 6.03
208V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 1.00 1.00 1.00 1.50 1.50 1.50
208V Total Amps 2.05 2.05 2.07 2.07 2.79 2.63 4.15 4.92 6.66 6.66
230V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 0.75 0.75 1.00 1.50 1.50 1.50
230V Total Amps 1.85 1.85 1.88 1.88 2.53 2.38 3.75 4.45 6.03 6.03
460V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 0.75 0.75 1.00 1.50 1.50 1.50
460V Total Amps 0.93 0.93 0.94 0.94 1.26 1.19 1.88 2.23 3.01 3.01
575V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 0.75 0.75 0.50 0.50 1.00 1.00
575V Total Amps 0.74 0.74 0.75 0.75 1.01 0.95 1.50 1.78 2.41 2.41
INSTALLATION - ELECTRICAL CONNECTIONS
Table 15.1 - Propeller Unit Model HD and Blower Unit Model HDB Operating Electrical Data
ELECTRICAL CONNECTIONS
1. Disconnect power supply before making wiring connections
to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a hazard
to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
cAUTION
Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% less than the rated voltage.
1. Installation of wiring must conform with local building codes,
or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 - Latest Edition. Unit must be electri cally
grounded in conformance to this code. In Canada, wiring
must comply with CSA C22.1, Part 1, Electrical Code.
W
ARNING
Amp draw data shown is operating amp draw at incoming power. For units that use a field installed accessory step-down transformer as noted, the amp draw shown is the primary side
operating amp draw. For sizing of circuit protection for equipment with transformers, please refer to the National Electric Code.
2. Two copies of the unit wiring diagram are provided with each
unit. One is located in the side access control compartment
and the other is supplied in the literature packet. Refer to
this diagram for all wiring connections.
3. Make sure all multi-voltage components (motors, transform-
ers, etc.) are wired in accordance with the power supply
voltage.
4. The power supply to the unit must be protected with a fused
or circuit breaker switch.
5. The power supply must be within 5 percent of the voltage
rating and each phase must be balanced within 2 percent of
each other. If not, advise the utility company.
6. External electrical service connections that must be installed
include:
a. Supply power connection (115, 208, 230, 460, or 575 volts).
b. Connection of thermostats, or any other accessory control
devices that may be supplied (24 volts).
NOTE: All units with supply voltage 208V and greater must use
a field installed step-down transformer, available as a separate
accessory. Refer to Table 15.1 for additional information on the
required transformer.
7. Refer to Figures 18.1 and 18.2 for the side access control
compartment location.
8. All supply power electrical connections are made in the side
access control compartment of the unit. The low voltage
(thermostat and accessory control devices) can be wired to
the terminals in the side access control compartment. Refer
to the wiring diagram for the terminal location of all low
voltage wiring.