Submittal Sheet

An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of
overheating.
A time delay relay that delays the start of the air mover to allow the heat exchanger a warm-up period after a call
for heat. The time delay relay shall also continue the air mover operation after the thermostat has been satisfied
to remove any residual heat in the heat exchanger.
The unit shall be orificed for 0-2000 feet elevation above sea level.
Electrical
All electrical components shall carry UL, ETL, or CSA listing.
A low voltage terminal board shall be provided for direct wiring connection to an external thermostat.
A single 115V to 24V step down transformer shall be provided for all unit controls.
Air Mover
The motor horsepower shall be 1/12 H.P.
The motor wiring shall be in flexible metal BX conduit.
The motor shall be controlled by a time delay relay.
Propeller models shall meet the following requirements:
The motor type shall be Single-Speed, Open Drip Proof (ODP).
The air mover motor shall be a 115V motor.
Mounting
The unit shall be equipped with mounting brackets to allow for threaded rod suspension or to be bolted directly to
the ceiling support structure allowing 1” of top clearance.
Accessories
The following field installed accessory control devices shall be provided with the unit: