Installation and Service Manual
Table Of Contents
13
6-584.13
INSTALLATION - HIGH ALTITUDE ACCESSORY KIT
HIGH ALTITUDE ACCESSORY KIT
Altitude (ft)
Gas Heating Values at Altitude (BTU/ft
3
)
USA Canada
0-2,000 1,050 1,050
2,001-3,000 929
9453,001-4,000 892
4,001-4,500 874
4,501-5,000 856 856
5,001-6,000 822 822
6,001-7,000 789 789
7,001-8,000 757 757
8,001-9,000 727 727
9,001-10,000 698 698
Altitude (ft)
Gas Heating Values at Altitude (BTU/ft
3
)
USA Canada
0-2,000 2,500 2,500
2,001-3,000 2,212
2,2503,001-4,000 2,123
4,001-4,500 2,080
4,501-5,000 2,038 2,038
5,001-6,000 1,957 1,957
6,001-7,000 1,879 1,879
7,001-8,000 1,803 1,803
8,001-9,000 1,731 1,731
9,001-10,000 1,662 1,662
Table 13.1 - Natural Gas Heating Values at  
Altitude 
jlm
Table 13.2 - Propane Gas Heating Values at 
Altitude 
klm
Modine’s gas-fired equipment standard input ratings are 
certified by ETL. For elevations above 2,000', ANSI Z223.1 
requires ratings be reduced 4 percent for each 1000' above sea 
level. For units in Canada, CSA requires that ratings be reduced 
10 percent at elevations above 2,000'. The high altitude 
adjustment instructions and pressure switch kits listed in this 
manual are for use with units that will be installed over 2,000' 
These methods and kits comply with both ANSI Z223.1 and 
CSA requirements.
If a unit is to be installed at higher elevations AND converted from 
natural gas to propane gas operation, a propane conversion kit 
must be used in conjunction with the pressure adjustment 
methods and pressure switch kits listed herein. For the selection 
and installation instructions for propane conversion kits, please 
see the latest revision of Modine Manual 75-515.
Selection of the Proper Pressure and Kit
To determine the proper manifold pressure at altitude and if 
required, the proper combustion air pressure switch kit, the full 
model number of the heater, the fuel to be used, and the 
altitude the unit will be installed at must be known. Refer to the 
unit serial plate or carton label to obtain the necessary 
information about the unit.
After obtaining this information, refer to the gas pressure and 
selection charts shown in Tables 13.1 through 13.3. The pressure 
charts are differentiated by elevation, fuel type, and country  
the product is being installed in. The selection charts are 
differentiated by product type, altitude and fuel type. If 
converting from natural gas to propane gas and operation 
at high altitude, both a propane conversion kit and a 
pressure switch kit must be used (if applicable). Selection 
charts include the proper kit suffix, when required.
Manifold Pressure Adjustment
The inlet pressure to the unit must be confirmed to be within 
acceptable limits (6-7" W.C. for natural gas and 11-14" W.C. for 
propane gas) before opening the shutoff valve or the 
combination gas valve may be damaged.
Heaters for the use with natural gas have gas valves that need 
to be field adjusted to 3.5" W.C. manifold pressure at 7.0" W.C. 
inlet pressure. 
Units for use with propane gas have gas valves that need to be 
field adjusted to 10.0" W.C. manifold pressure at 14.0" W.C. 
inlet pressure. 
Installation above 2,000' elevation requires adjustment of the 
manifold pressure as described.
Derated BTU Content Gas and Manifold Pressure 
Calculation
Some utility companies may derate the BTU content (heating 
value) of the gas provided at altitude to a value other than 1,050 
BTU/ft
3
 for natural gas or 2,500 BTU/ft
3
 for propane gas to allow 
certain heating appliances to be used with no manifold pressure 
adjustments. For this reason it is necessary that the supplying 
utility be contacted for detailed information about the gas type 
and BTU content (heating value) before operating any heater. 
Tables 13.1 and 13.2 show the standard derated heating values 
(4% per 1,000' of elevation in the USA and 10% between 2,001' 
and 4,500' elevation in Canada) of natural and propane gases 
at various altitudes. If the utility is supplying gas with heating 
values as shown in Tables 13.1 and 13.2, the manifold pressure 
should be set to 3.5" W.C for natural gas and 10.0" W.C. for 
propane gas. 
NOTE: Only the high fire gas pressure need be adjusted, low 
fire gas pressure should remain the same.
j
 Values shown are for 3.5" W.C. manifold pressure, for other BTU content values (available from local utility) use Equation 14.1 to calculate manifold pressure. 
k
 Values shown are for 10.0" W.C. manifold pressure, for other BTU content values (available from local utility) use Equation 14.1 to calculate manifold pressure. 
l
 When installed at altitudes above 2,000', a pressure switch may need to be changed. Refer to Table 13.3 to determine if a switch change is required. 
m
 Gas heating values are derated 4% per 1,000' of elevation in the USA and 10% between 2,000' and 4,500' elevation in Canada in accordance with ANSI Z223.1 
and CSA-B149, respectively.
Table 13.3 - High Altitude Kits for HDS/HDC 
j
Model 
Size
Details
U.S.A and Canada
0-2,000 ft 2,001-2,500 ft 2,501-4,500 ft 4,501-5,500 ft 5,501-6,500 ft 6,501-7,500 ft 7,501-8,500 ft 8,501 - 9,500 ft 9,501-10,000 ft
30
Kit Sufx
Not Required Label Only Label Only
0003 0005 0005 0010 0010 0010
Item Code 68407 68409 68409 68414 68414 68414
45
Kit Sufx
Not Required Label Only
0002 0004 0003 0006 0010 0010 0011
Item Code 68406 68408 68407 68410 68414 68414 68415
60
Kit Sufx
Not Required Label Only
0003 0003 0005 0007 0011 0011 0011
Item Code 68407 68407 68409 68411 68415 68415 68415
75
Kit Sufx
Not Required Label Only
0003 0003 0005 0007 0011 0011 0011
Item Code 68407 68407 68409 68411 68415 68415 68415
100
Kit Sufx
Not Required Label Only Label Only Label Only Label Only
0004 0004 0004 0004
Item Code 68408 68408 68408 68408
125
Kit Sufx
Not Required Label Only Label Only Label Only
0004 0004 0004 0004 0004
Item Code 68408 68408 68408 68408 68408
j
 For Label Only kits, Modine part number 5H0807146005 is required to be lled out and attached to the unit by the installer. Please contact the local Modine  
representative at 1.866.828.4328 (HEAT).










