ELECTRICAL CONNECTIONS
Location of thermostat should be determined by heating 
requirements and be mounted on an inside wall about 5' above 
floor level where it will not be affected by heat from the unit 
or other sources, or drafts from frequently opened doors. See 
instructions packed with thermostat.
Wiring Adjustments for Blower Motors
The blowers used on Modine HDC units are direct drive and 
equipped with three speed motors. Air temperature rise of the 
unit is determined by the speed setting and the amount of static 
pressure in the system. Units are normally shipped with motors set 
at high speed. Motor speed is changed by connecting the motor 
lead for the desired fan speed to the “EAC” or “Blo” terminal of the 
control board. Unused motor leads for other speeds are placed on 
the “Park” terminals of the board. See the wiring diagram on 
page 21. 
When applying a blower equipped unit to a duct system or other 
load, consult the performance curves on this page to determine 
the air temperature rise for a given motor speed range and static 
pressure. Verify that the static pressure on the outlet of the unit 
does not exceed the maximum specified for the unit. If static 
pressure is too high it must be reduced either by modifications to 
the system or using the medium or low motor speed. If the unit 
shuts down on high limit during normal operation, a higher motor 
speed should be used.
INSTALLATION - ELECTRICAL CONNECTIONS
Blower Curve Models (HDC 60-125 Only)
Speeds
Low Medium High
65
60
55
50
45
40
35
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
1140
1235
1347
1481
1646
1852
2116
External Static Pressure (IN. WC)
Temperature Rise (Deg. F)
HDC 100
CFM
70
65
60
55
50
45
40
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
1235
1323
1425
1543
1684
1852
2058
2315
External Static Pressure (IN. WC)
Temperature Rise (Deg. F)
75
HDC 125
CFM
70
65
60
55
50
45
40
35
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
794
855
926
1010
1111
1235
1389
1587
External Static Pressure (IN. WC)
Temperature Rise (Deg. F)
CFM
HDC 75
70
65
60
55
50
45
40
35
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
635
684
741
808
889
988
1111
1270
External Static Pressure (IN. WC)
Temperature Rise (Deg. F)
CFM
HDC 60