Figure 18.2 - Unit Heater Rear View
CONTROL OPERATING SEQUENCE / UNIT COMPONENTS
Upon a call for heat from the thermostat, power is supplied to 
the power exhauster motor. The unit will go through a purge 
period and then the direct spark igniter will be energized. At the 
same time, the main valve in the combination control valve will 
open to allow gas to flow to the burners. If the fan motor has not 
already started it will start shortly. If a flame is not sensed for 
any reason the main valve will close and there will be a short 
purge period before ignition is tried again. If the flame is not 
sensed after 4 tries there will be at least a one hour wait before 
ignition is tried again.
CONTROL OPERATING SEQUENCE
Figure 18.1 - Major Gas, Electrical Service, Safety and Other Components
1. Power Exhauster
2. Pressure Switch
3. Integrated Direct Spark Control Board
4. Combination Gas Control
5. Control Transformer
6. Flame Sensor (hidden)
7. Flame Rollout Switch
8. Auto Reset Limit Control (hidden)
9. Direct Spark Igniter (hidden)
10.  Manual Reset Control (hidden, 
propeller 100-125 only)
j
k
l
m
n
o
p
q
r
s
Vent Pipe Connection
Gas Pipe
Access Panel with 
Lighting / Operating 
Instructions
Electrical Access 
Holes
Fingerproof Fanguard
Fan Motor
Mounting Brackets
Table 18.1 - Control Options
Control Description
  Control  Service  Thermostat  Type of  Model
 Code No.  Voltage  Voltage  Gas  Size
Single-Stage, Direct Spark Ignition, 100% Shut-Off with Continuous Retry  11  115V  24V  natural 30-125
- Utilizes a single-stage combination gas control with ignition control. 
Gas is lit with a direct spark igniter on call for heat.  21  115V  24V  propane 30-125
Two-Stage, Direct Spark Ignition, 100% Shut-Off with Continuous Retry  12  115V  24V  natural  75-125
- Utilizes a two-stage combination gas control with built-in ignition control. 
Firing rate is 100% and 50% of full rated input. Gas is lit with a direct spark 
22  115V  24V  propane 75-125
igniter on call for heat.
Combustion Air Inlet 
Pipe Connection
Flame 
Sight Glass