SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS 
MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT 
AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR 
CARE MUST BE EXERCISED REGARDING THE SPECIAL 
PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS 
THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE 
OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS 
SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL 
CODES.
HAZARD INTENSITY LEVELS
1.  DANGER: Indicates an imminently hazardous situation   
  which, if not avoided, WILL result in death or serious injury.
2.  WARNING: Indicates a potentially hazardous situation   
  which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,   
if not avoided, MAY result in minor or moderate injury.
4.  IMPORTANT: Indicates a situation which, if not avoided,   
  MAY result in a potential safety concern. 
  DANGER
Appliances must not be installed where they may be exposed 
to a potentially explosive or flammable atmosphere.
  WARNING
1.  Gas fired heating equipment must be vented - do not   
  operate unvented.
2.  A built-in power exhauster is provided - additional external  
  power exhausters are not required or permitted.
3.  If an existing heater is being replaced, it may be necessary 
  to resize the venting systems. Improperly sized venting   
  systems can result in vent gas leakage or the formation of  
  condensate. Refer to the National Fuel Gas Code ANSI   
  Z223.1 (NFPA 54) or CSA B149.1 latest edition. Failure to 
  follow these instructions can result in injury or death.
4.  Under no circumstances should two sections of double wall  
  vent pipe be joined together within one horizontal vent system  
  due to the inability to verify complete seal of inner pipes. 
5.  All field gas piping must be pressure/leak tested prior to   
  operation. Never use an open flame. Use a soap solution  
  or equivalent for testing.
6.  Gas pressure to appliance controls must never exceed 
  14" W.C. (1/2 psi).
7.  To reduce the opportunity for condensation, the minimum   
  sea level input to the appliance, as indicated on the serial  
  plate, must not be less than 5% below the rated input,   
  or 5% below the minimum rated input of dual rated units. 
8.  Disconnect power supply before making wiring connections 
  to prevent electrical shock and equipment damage.
9.  All appliances must be wired strictly in accordance with   
  wiring diagram furnished with the appliance. Any wiring   
  different from the wiring diagram could result in a hazard to 
  persons and property. 
10. Any original factory wiring that requires replacement must 
  be replaced with wiring material having a temperature   
  rating of at least 105°C.
11. Ensure that the supply voltage to the appliance, as indicated 
  on the serial plate, is not 5% greater than the rated voltage.
12. When servicing or repairing this equipment, use only   
  factory-approved service replacement parts. A complete   
  replacements parts list may be obtained by contacting   
  the factory. Refer to the rating plate on the appliance for   
  complete appliance model number, serial number, and   
  company address. Any substitution of parts or controls not  
  approved by the factory will be at the owner's risk.
  CAUTION
1.  All literature shipped with this unit should be kept for   
  future use for servicing or service diagnostics. Do not   
  discard any literature shipped with this unit.
2.  Consult piping, electrical, and venting instructions in this   
  manual before final installation.
3.  Do not attach ductwork, air filters, or polytubes to any   
  propeller unit heater.
4.  Clearances to combustible materials are critical. Be sure to   
  follow all listed requirements.
5.  Low profile heaters are designed for use in heating applica- 
   tions with ambient startup temperatures between -40°F and 
90°F, and ambient operating temperatures between 40°F 
and 90°F. 
6.  Do not install unit outdoors.
7.  In garages or other sections of aircraft hangars such  
  as offices and shops that communicate with areas used for  
  servicing or storage, keep the bottom of the unit at least  
  7' above the floor unless the unit is properly guarded  
  to provide user protection from moving parts. In parking  
  garages, the unit must be installed in accordance with  
  the standard for parking structures ANSI/NFPA 88A latest   
   edition, and in repair garages the standard for repair garages 
NFPA 30A - latest edition (Formerly NFPA 88B). In Canada, 
installation of heaters in airplane hangars must be in 
accordance with the requirements of the enforcing authority, 
and in public garages in accordance with the current CSA-
B149 codes.
8.  In aircraft hangars, keep the bottom of the unit at least 10'   
  from the highest surface of the wings or engine enclosure   
  of the highest aircraft housed in the hangars and in   
  accordance with the requirements of the enforcing authority 
  and/or NFPA 409-latest edition.
9.  Installation of units in high humidity or salt water     
  atmospheres will cause accelerated corrosion resulting in a  
  reduction of the normal life of the units.
10. Do not install units below 7' measured from the bottom of   
  the unit to the floor in commercial applications (unless 
  unit is properly guarded to provide user protection from   
  moving parts) and 5' measured from the bottom of the unit   
  to the floor in residential applications.
11. Be sure no obstructions block air intake and discharge of   
  unit heaters.
12. The minimum distance from combustible material is based  
  on the combustible material surface not exceeding 160°F.   
  Clearance from the top of the unit may be required to be   
  greater then the minimum specified if heat damage, other   
  than fire, may occur to materials above the unit heater at   
  the temperature described.
13. Allow 18" of clearance at rear (or 6" beyond end of motor at  
  rear of unit, whichever is greater) and access side to   
  provide ample air for proper operation of fan.
14. Installation must conform with local building codes or in the  
absence of local codes, with the National Fuel Gas 
Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada 
installation must be in accordance with CSA-B149.1.
15.  The concentric vent adapter box must be installed inside 
of the structure or building. Do not install this box on the 
exterior of a building or structure. 
16.  Purging of air from gas supply line should be performed as  
described in the National Fuel Gas Code, ANSI Z223.1 
(NFPA 54) - latest edition, or, or in Canada in CSA-B149 
codes.
17. When leak testing the gas supply piping system, the   
  appliance and its combination gas control must be isolated 
  during any pressure testing in excess of 14" W.C. (1/2 psi).