Installation and Service Manual
Table Of Contents
6-584.13
UNIT LOCATION
Location Recommendations
1.  When locating the heater, consider general space and 
heating requirements, availability of gas and electrical 
supply, and proximity to vent locations.
2.  When locating units, it is important to consider that the 
combustion air and exhaust vent piping must be connected 
to the outside atmosphere. Vent terminals should be located 
adjacent to one another. Maximum equivalent vent lengths 
are listed in “Section A - General Instruction - All Units” of the 
venting instructions.
3.  Be sure the structural support at the unit location site is 
adequate to support the unit's weight. For proper operation 
the unit must be installed in a level horizontal position.
4.  Do not install units in locations where the flue products 
can be drawn into the adjacent building openings such as 
windows, fresh air intakes, etc.
5.  Be sure that the minimum clearances to combustible 
materials and recommended service clearances are 
maintained. Units are designed for installation with the 
minimum clearances as shown in Table 4.1.
Table 4.1 - Clearances
6. Do not install units in locations where gas ignition system is 
exposed to water spray, rain, or dripping water.
7. Mounting height (measured from bottom of unit) at which unit 
heaters are installed is critical. Refer to mounting height and 
heat throw data on page 16 of this manual. The maximum 
mounting height for any unit is that height above which the 
unit will not deliver heated air to the floor. 
Turning The Unit 180° (Model sizes 30-75 only)
All units are produced at the factory with left-side controls (when 
looking at the unit). If the installation requires the controls to 
be on the right side, all HDS/HDC heaters - with the exception 
of the 100 and 125 - can be turned-over by following the 
instructions below.
•  By turning the unit 180° from the way it was received from 
the factory, the sides become opposite but the front and 
back remain in the same relative position. The bottom 
panel now becomes the top panel and vice-versa.
•  Remove the access panel, turn it 180°, and re-attach it to 
the unit so that all the information labels can be read.
•  Remove the spring-loaded deflector blades, turn them over, 
replace, and adjust so they are open and in a position to 
direct the heated air down to the floor.
UNIT LOCATION 
4
 DANGER
Appliances must not be installed where they may be exposed 
to a potentially explosive or flammable atmosphere.
IMPORTANT
To prevent premature heat exchanger failure, do not locate   
ANY gas-fired appliances in areas where corrosive vapors   
(i.e. chlorinated, halogenated or acid) are present in the   
atmosphere.
 CAUTION
1. Clearances to combustible materials are critical. Be sure to   
  follow all listed requirements.
2. Low profile heaters are designed for use in heating 
applications with ambient startup temperatures between 
-40°F and 90°F, and ambient operating temperatures 
between 40°F and 90°F.
3. Do not install unit outdoors.
4. In garages or other sections of aircraft hangars such 
as offices and shops that communicate with areas used for 
servicing or storage, keep the bottom of the unit at least 
7' above the floor unless the unit is properly guarded. 
 In parking garages, the unit must be installed in accordance 
with the standard for parking structures ANSI/NFPA 
88A-latest edition, and in repair garages the standard for 
repair garages NFPA 30A - latest edition (Formerly NFPA 
88B). In Canada, installation of heaters in airplane 
hangars must be in accordance with the requirements 
of the enforcing authority, and in public garages in 
accordance with the current CSA-B149 codes.
5. In aircraft hangars, keep the bottom of the unit at least 10'   
  from the highest surface of the wings or engine enclosure 
  of the highest aircraft housed in the hangars and in   
  accordance with the requirements of the enforcing authority 
  and/or NFPA 409-latest edition.
6. Installation of units in high humidity or salt water 
atmospheres will cause accelerated corrosion, resulting in 
a reduction of the normal life of the units.
Recommended Service
Clearance
HDS HDC HDS/HDC
Top and Boom 1" 6" 18"
Access Side 1" 6" 18"
Non
Access Side 1" 6" 18"
Rear 18" 18" 18"
Vent Connector 4" 4" 18"
Unit Side
Clearance to
Combusble Material










