Installation and Service Manual
Table Of Contents
6
6-584.13
Model HDS/HDC unit heaters must be vented with the proper 
passageway as described in these instructions to convey 
flue gases from the unit or the vent connector to the outside 
atmosphere. The heaters must also have a separate combustion 
air intake pipe to bring in fresh air for combustion from the 
outside atmosphere. 
The venting instructions are organized in sections, based on 
installation type. The sections are identified as follows:
  Instructions  Applicable Installation Instructions
  Section  by Vent System Type
  A  General instructions for ALL installations
 B  VERTICAL 2-PIPE vent systems j
 C  HORIZONTAL 2-PIPE vent systems j
 D  HORIZONTAL AND VERTICAL  
  CONCENTRIC vent systems j
j The differences between vertical and horizontal vent systems in 2-Pipe or 
concentric vent configurations will be identified in “Section A - General 
Instructions – All Units”. 
Section A – General Instructions – All Units
A1. If the unit heater being installed is replacing existing 
equipment and using the existing vent system from that 
equipment, inspect the venting system for proper size and 
horizontal pitch, as required in the National Fuel Gas Code 
ANSI Z223.1 or CSA B149.1 Installation Code-latest edition 
and these instructions. Determine that there is no blockage 
or restriction, leakage, corrosion and other deficiencies, 
which could cause an unsafe condition.
A2. The combustion air pipe and vent pipe should be galvanized 
steel or other suitable corrosion resistant material. Follow 
the National Fuel Gas Code for minimum thickness of vent 
material. The minimum thickness for connectors varies 
depending on the pipe diameter. Do not vent unit with PVC 
or other forms of plastic venting material.
A3. All heaters come with factory installed vent and combustion 
air adapters for attaching the vent pipe to the heater. Attach 
the vent pipe to the adapter with 3 corrosion resistant 
screws. (Drill pilot holes through the vent pipe and adapter 
prior to screwing in place). Vent pipe must not be smaller 
than the connector size.
A4.   Refer to Table 6.1 for total equivalent vent pipe lengths, 
making the vent system as straight as possible. The 
equivalent length of a 3” elbow is 1’ and for a 4” elbow is 5’.
A5. A minimum of 12" straight pipe is recommended from the 
flue outlet before turns in the vent pipe. 
A6. Horizontal sections of vent pipe are to be installed with an 
upward or downward slope from the appliance of 1/4" per 
foot and suspended securely from overhead structures at 
points not greater than 3' apart.
A7. Fasten individual lengths of vent together with at least 3 
corrosion-resistant sheet metal screws.
A8. Keep single wall vent pipe at least 6" from combustible 
materials. For double wall vent pipe, follow the vent 
pipe manufacturer’s clearances to combustibles. The 
minimum distance from combustible materials is based 
on the combustible material surface not exceeding 160°F. 
Clearance from the vent pipe (or the top of the unit) may be 
required to be greater than 6" if heat damage other than fire 
could result (such as material distortion or discoloration).
A9. Avoid venting through unheated space when possible. 
When venting does pass through an unheated space or 
if the unit is installed in an environment that promotes 
condensation, insulate runs greater than 5' to minimize 
condensation. Inspect for leakage prior to insulating and use 
insulation that is noncombustible with a rating of not less 
than 400°F. Install a tee fitting at the low point of the vent 
system and provide a drip leg with a clean out cap as shown 
in Figure 8.1.
INSTALLATION - VENTING
  WARNING
1. Gas fired heating equipment must be vented - do not 
operate unvented.
2.  A built-in power exhauster is provided - additional external 
power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary 
to resize the venting systems. Improperly sized venting 
systems can result in vent gas leakage or the formation of 
condensate. Refer to the National Fuel Gas Code ANSI 
Z223.1 (NFPA 54) or CSA-B149.1 Installation Code - latest 
edition. Failure to follow these instructions can result in 
serious injury or death.
4.  Under no circumstances should 2 sections of double wall 
vent pipe be joined together within 1 horizontal vent system 
due to the inability to verify complete seal of inner pipes.
 CAUTION
Installation must conform with local building codes or in the 
absence of local codes, with Part 7, Venting of Equipment, of 
the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest 
edition. In Canada installation must be in accordance with 
CSA B149.1.
Figure 6.1 - Venting Through Combustible Roof or Wall
Flashing
Listed
Thimble
Listed
Terminal
Listed
Terminal
Flashing
Clearance Specified 
by Type B Vent Mfg.
Listed
Thimble
Single Wall Vent Pipe
Double Wall Vent Pipe 
j
Single Wall Vent Pipe Terminating 
with Double wall vent pipe. 
j
Single Wall Vent Pipe
j
 See Instruction A12 for attaching single wall pipe to double wall pipe.
Double 
Wall
Single 
Wall
Listed
Terminal
Clearance Specified 
by Type B Vent Mfg.
Single 
Wall
Listed
Terminal
Table 6.1 - Vent Pipe Diameters, Transitions, and
Total Equivalent Vent Pipe Lengths For Horizontal
and Vertical Venting Systems
Model 
Size
Vent Pipe 
Sizes
Minimum
Eqv. Length
Maximum
Eqv. Length
30-45 3" 3' 25'
60-125 4" 3' 25'










