Installation and Service Manual
Table Of Contents
6-584.13
A10. When the vent passes through a combustible INTERIOR 
wall or floor, a metal thimble 4" greater than the vent 
diameter is necessary. If there is 6' or more of vent pipe in 
the open space between the appliance and where the vent 
pipe passes through the wall or floor, the thimble need only 
be 2" greater than the diameter of the vent pipe. If a thimble 
is not used, all combustible material must be cut away 
to provide 6" of clearance. Where authorities have 
jurisdiction type B vent may be used for the last section 
of vent pipe to maintain clearance to combustibles while 
passing through wall or floor (see Figure 6.1). Any material 
used to close the opening must be noncombustible.
A11. Seal all seams and joints of un-gasketed single wall pipe 
with metal tape or Silastic suitable for temperatures up to 
400°F. Wrap the tape 2 full turns around the vent pipe. One 
continuous section of double wall vent pipe may be used 
within the vent system to pass through the wall to a listed 
vent cap. Refer to instruction A12 in “Section A – General 
Instructions – All Units” for attaching double wall pipe to 
single wall pipe. 
A12. The following are general instructions for double wall (type 
B) terminal pipe installation:
How to attach a single wall vent terminal to double wall 
(type B) vent pipe:
1.  Look for the “flow” arrow on the vent pipe. 
2.  Slide the vent terminal inside the exhaust end of the 
double wall vent pipe.
3.  Drill 3 holes through the pipe and the vent terminal. 
Using 3/4" long sheet metal screws, attach the cap to 
the pipe. Do not overtighten.
How to connect a single wall vent system to a double 
wall (type B) vent pipe: 
1.  Slide the single wall pipe inside the inner wall of the 
double wall pipe.
2.  Drill 3 holes through both walls of the single and double 
wall vent pipes. Using 3/4" sheet metal screws, attach 
the 2 pieces of pipe. Do not overtighten. 
3.  The gap between the single and double wall pipe must 
be sealed but it is not necessary to fill the full volume 
of the annular area. To seal, run a large bead of 400°F 
silastic around the gap.
A13. Vent termination clearances must be maintained:
A14. Do NOT vent this appliance into a masonry chimney. 
A15. Do NOT use dampers or other devices in the vent or 
combustion air pipes.
A16. 
The venting system must be exclusive to a single 
appliance, and no other appliance is allowed to be vented 
into it.
A17. Precautions must be taken to prevent degradation of 
building materials by flue products.
A18. Single wall vent pipe must not pass through any 
unoccupied attic, inside wall, concealed space, or floor.
A19. Uninsulated single wall vent pipe must not be used 
outdoors for venting appliances in regions where the 99% 
winter design temperature is below 32°F.A19. Long runs 
of horizontal or vertical combustion air pipes may require 
insulation in very cold climates to prevent the buildup of 
condensation on the outside of the pipe where the pipe 
passes through conditioned spaces.
A20. Vertical combustion air pipes should be fitted with a tee 
with a drip leg and a clean out cap to prevent against the 
possibility of any moisture in the combustion air pipe from 
entering the unit. The drip leg should be inspected and 
cleaned out periodically during the heating season.
A21. The vent terminal must be:
A22. In addition to following these general instructions, specific 
instructions for vertical and horizontal vent systems in 
2-Pipe or concentric vent configurations must also be 
followed. The following outlines the differences:
Vertical Category III Vent System Determination
•  Vertical vent systems terminate vertically (up) (an example is 
shown in Figure 8.1).
•  Determine the venting configuration as follows: 
  > For two building penetrations through the wall or roof (one 
for the combustion air inlet pipe and one for the vent pipe), 
proceed to “Section B - Vertical 2-Pipe Venting”.
  > For a single larger building penetration through the wall or 
roof, through which both the combustion air inlet and vent 
pipes will pass, proceed to “Section D - Horizontal and 
Vertical Concentric Venting”. 
  > For all other cases, proceed to the next section for 
Horizontal Vent System Determination.
Horizontal Category III Vent System Determination
•  Horizontal vent systems terminate horizontally (sideways) 
(an example is shown in Figure 9.1).
•  Determine the venting configuration as follows:
  > For two building penetrations through the wall or roof (one 
for the combustion air inlet pipe and one for the vent pipe), 
proceed to “Section C - Horizontal 2-Pipe Venting”.
  > For a single larger building penetration through the wall or 
roof, through which both the combustion air inlet and vent 
pipes will pass, proceed to “Section D - Horizontal and 
Vertical Concentric Venting”.
7
INSTALLATION - VENTING
  Minimum Clearances for
  Structure  Vent Terminal Location 
Forced air inlet within 10 feet  3 feet above
Combustion air inlet of another 
appliance  6 feet all directions
Door, window, gravity air inlet,  4 feet horizontal and below
or any building opening  1 foot above
Electric meter, gas meter, gas  4 feet horizontal (U.S.)
regulator, and relief equipment 
j
 6 feet horizontal (Canada)
Gas regulator 
j
  3 feet horizontal (U.S.)
  6 feet horizontal (Canada)
Adjoining building or parapet wall  6 feet all directions
Adjacent public walkways  7 feet all directions
Grade (ground level)  3 feet above
Table 7.1 - Vent Termination Clearances
j Do not terminate the vent directly above a gas meter or regulator.
Table 7.2 - Vent Terminals (two pipe)
Model Size Modine PN
30-45 5H0722850005
60-75 5H0722850001
100-125 5H0722850001










