Installation and Service Manual

Table Of Contents
19
6-584.13
DIMENSIONS / GENERAL PERFORMANCE DATA - HDS/HDC
Table 19.1 - Dimensions (inches)
Dimension
Propeller Model Size - HDS Blower Model Size - HDC
30 45 60 75 100 125 60 75 100/125
A 26.8 26.8 26.8 26.8 35.5 35.5 26.8 26.8 35.5
B 12.2 12.2 18 18 20.5 20.5 18 18 20.5
C 16.5 16.5 16.5 16.5 22 22 16.5 16.5 22
D 14.9 14.9 14.9 14.9 22.5 22.5 14.9 14.9 22.5
E 10.1 10.1 15.9 15.9 18.4 18.4 15.9 15.9 18.4
F 7.25 7.25 10.75 10.75 14 14 10.75 10.75 14
G 18.5 18.5 18.5 18.5 - 18.5 18.5
H 7.6 7.6 7.835 7.835 8.4 8.4 7.835 7.835 8.4
I 34.5 34.5 34.5 34.5 43 43 35.5 35.5 44.5
J 22 22 25 25 30.67 30.74 32.5 32.5 41.5
K 2.74 2.74 3.15 3.15 3.87 3.87 3.15 3.15 3.87
L 3.19 3.19 5.55 5.55 10.73 10.73 5.55 5.55 10.73
Vent and Combustion Air
Connector Size
3 3 4 4 4 4 4 4 4
Gas Connection 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Fan or Blower Diameter 10 10 14 14 18 18 9 - 7 9 - 7 10 - 10
Approx. Weight (lbs.) 55 60 80 85 125 125 92 97 151
14.9" BETWEEN 3/8"-16 MOUNTING HOLES
(MODEL SIZES 100 AND 125 ONLY)
3.5"
10.0"
13.5" BETWEEN 3/8"-16 MOUNTING HOLES
(MODEL SIZES 100 AND 125 ONLY)
Figure 19.2 - Mounting Bracket Slot Locations
1” - angle, mounting brackets are slotted to accommodate joists on 16” or 24” centerlines.
HDS/HDC
30-75
HDS/HDC
100/125
(accessory)
.00
1.10
3.10
5.10
7.10
9.10
17.10
19.10
21.10
23.10
25.10
26.20
.00
1.50
3.50
5.50
7.50
9.50
11.50
13.50
21.50
23.50
25.50
27.50
29.50
31.50
33.50
35.00
HDS/HDC
30-75
HDS/HDC
100/125
(accessory)
.00
1.10
3.10
5.10
7.10
9.10
17.10
19.10
21.10
23.10
25.10
26.20
.00
1.50
3.50
5.50
7.50
9.50
11.50
13.50
21.50
23.50
25.50
27.50
29.50
31.50
33.50
35.00
Table 19.2 - Propeller Model HDS Performance
Table 19.3 - Blower Model HDC Performance
Model HDS Sizes
30 45 60 75 100 125
Btu/Hr Input 30,000 45,000 60,000 75,000 100,000 125,000
Btu/Hr Output 24,600 36,900 49,200 61,500 82,000 102,500
Entering Airow (CFM) @ 70°F 505 720 990 1160 1490 1980
Outlet Velocity (FPM) 523 725 653 769 565 747
Air Temp. Rise (°F) 44 46 45 48 50 47
Max. Mounting Height (Ft.) 10 10 12 14 12 16
Heat Throw (Ft.)
(@ Max Mtg Ht.)
25 27 36 38 42 56
Motor Type SP SP PSC PSC SP PSC
Motor HP 1/15 1/15 1/12 1/12 1/12 1/8
Motor RPM 1550 1550 1625 1625 1050 1625
Model HDC Sizes
60 75 100 125
Btu/Hr Input
j
60,000 75,000 100,000 125,000
Btu/Hr Output
j
49,200 61,500 82,00 102,500
Entering Airow Range (CFM) 635-1111 794-1389 1140-2116 1235-2058
Outlet Velocity (FPM) 437-726 546-908 443-781 488-773
Air Temp. Rise (°F) 40-70 40-70 35-65 45-75
Max. Mounting Height (Ft.)
k
7-13 7-16 8-19 8-17
Heat Throw (Ft.)
(@ Max Mtg Ht.)
k
20-45 24-57 27-68 27-59
Motor Type
l
P.S.C. P.S.C. P.S.C. P.S.C.
Motor HP 1/4 1/3 1/2 1/2
Motor RPM Max 1100 Max 1100 Max 1100 Max 1100
j
Ratings shown are for elevations up to 2,000 feet. For elevations above 2,000 feet,
ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (In
Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
k
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated
input. Mounting height as measured from bottom of unit, and without deflector hoods.
Figure 19.1 - Dimensional Drawings