Troubleshoot

ONE FLASH PRESSURE SWITCH WON’T CLOSE
Pressure switch does not close within 30 seconds of inducer energized
Unit sequence: Green light on, call for heat, 24 VAC at
R & W , power exhauster cycles on, after approx. 30
seconds, Green Light will give One Flash
Possible cause:
Blockage in tubing to pressure or venting not allowing
for a proper vacuum to pull pressure switch contacts
closed. Troubleshoot Venting.
Wire off pressure switch
24 VAC not coming from board.
Defective pressure switch (verify and replace)