Troubleshoot
Table Of Contents
- Troubleshooting HD Direct Spark Units
- How to use this application
- Table of contents
- Definitions & Basic Operation
- Flame Status - Yellow LED labeled “FLAME”
- Heating Sequence of operation
- End of Heating Sequence of operation
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Troubleshooting flash codes
- Troubleshooting flash codes
- No flashes – Troubleshooting codes
- One Flash - Troubleshooting codes
- One Flash – No Power Exhauster
- One Flash – Pressure switch Won’t close
- Two flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Five Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Seven Flashes - Troubleshooting codes
- Before REPLACING THE CONTROL BOARD
- For additional help Installation & Service manual live operators
- Slide Number 41
THREE FLASHES - TROUBLESHOOTING CODES
• Open in the safety switch circuit (limit switch or flame roll out
switch is open).
• Unit sequence:
• Green Light on, call for heat. Power exhauster cycles on.
• Fan Motor Cycles on. Green light starts three flashes.
• Possible cause:
• Open or short in safety circuit (flame roll out switches some and
some limit switches are manual reset).
– Check for open contacts on switch in safety circuit. Reset flame roll
out switches and manual reset limit switches
– Check wiring. Wire off limit or flame rollout switch. Limit or flame
rollout switch shorting to unit. Defective limit or flame rollout switch.
Verify and replace if required.
• Defective board, not letting 24 VAC through limits.
Back Start Over