Troubleshoot
Table Of Contents
- Troubleshooting HD Direct Spark Units
- How to use this application
- Table of contents
- Definitions & Basic Operation
- Flame Status - Yellow LED labeled “FLAME”
- Heating Sequence of operation
- End of Heating Sequence of operation
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Call for heat – unit does nothing
- Troubleshooting flash codes
- Troubleshooting flash codes
- No flashes – Troubleshooting codes
- One Flash - Troubleshooting codes
- One Flash – No Power Exhauster
- One Flash – Pressure switch Won’t close
- Two flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Three Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Four Flashes - Troubleshooting codes
- Five Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Six Flashes - Troubleshooting codes
- Seven Flashes - Troubleshooting codes
- Before REPLACING THE CONTROL BOARD
- For additional help Installation & Service manual live operators
- Slide Number 41
SIX FLASHES - TROUBLESHOOTING CODES
• Open in the safety switch circuit (limit switch or flame roll out
switch is open). Main air mover DOES NOT cycle on.
• Unit Sequence:
• Green Light on, call for heat Power exhauster cycles on, pre purge
• 24 volts power present through pressure switch, limits, and to valve
• Igniter Sparks, burner cycles on, yellow flame light on board is on.
• After 3 to 4 minutes , unit goes out on a limit switch, yellow light off,
green light will flash six times.
• Possible cause:
• Check all wiring, loose wire
• Defective motor, 115 VAC present at EAC & Neutral terminals on
board, but motor does not run.
• Defective board, 115 VAC not present at EAC and Neutral terminals
Back Start Over