Standard Models Low-Outlet Temperature Models
Steam Hot Water Steam
(2# Steam) (200°F In, 180°F Out) (2# Steam)
Heat Heat
Final Final Max. Throw @ Final Max. Throw @
➂ Air Water Air Mtg. Max. Mtg. Air Mtg. Max. Mtg.
Motor Temp. Flow Temp. Height Height Temp. Height Height
Model Number HP Btu/Hr (°F) Btu/Hr (GPM) (°F) CFM (Ft) (Ft) Model Number Btu/Hr CFM (°F) (Ft) (Ft)
HSB/HC 18 1/60 18,000 107 12,560 1.3 94 340 9 18 HSB/HC 18L 15,900 364 100 9 20
HSB/HC 24 1/25 24,000 119 16,250 1.7 100 370 10 19 HSB/HC 24L 19,300 435 100 11 21
HSB/HC 33 1/25 33,000 108 21,680 2.3 91 630 11 22 HSB/HC 33L 29,500 695 99 12 24
HSB/HC 47 1/12 47,000 119 30,940 3.2 98 730 13 30 HSB/HC 47L 32,000 855 94 14 32
HSB/HC 63 1/12 63,000 111 45,580 4.7 97 1120 15 31 HSB/HC 63L 52,500 1170 101 16 33
HSB/HC 86 1/8 86,000 118 60,210 6.3 101 1340 16 33 HSB/HC 86L 61,500 1510 97 17 36
HSB/HC 108 1/8 108,000 109 83,740 8.7 98 2010 18 33 HSB/HC 108L 86,500 2150 97 19 36
HSB/HC 121 1/5 121,000 122 93,000 9.7 108 1775 17 27 HSB/HC 121L 88,000 2070 98 18 29
HSB/HC 165 1/3 165,000 106 130,950 13.6 97 3240 20 43 HSB/HC 165L 143,000 3480 97 21 45
HSB/HC 193 1/3 193,000 121 143,000 14.9 105 2900 19 40 — — — — —
HSB/HC 258 1/2 258,000 111 201,950 21 100 4560 20 47 HSB/HC 258L 190,000 4655 98 22 51
HSB/HC 290 1/2 290,000 117 228,620 23.8 105 4590 21 49 HSB/HC 290L 207,000 5040 94 23 53
HSB/HC 340 1/2 340,000 120 271,110 28.2 108 5130 21 49 HSB/HC 340L 255,000 5575 102 23 53
2
HORIZONTAL AIR DELIVERY MODELS
HSB and HC models feature the following:
Squared off corners for a clean, smooth appearance.
HSB models have top and bottom supply and return steel connections.
HC models have a copper tube and copper coil connections located on the side for low
clearance applications.
A two piece casing for quick access to coil.
An electric junction box for easy electrical connections.
Baked on gray-green, electrostatically applied polyester powdercoat, environmentally
friendly paint.
Motors are totally enclosed with thermal overload protection.
Low outlet temperature models for higher steam pressures or dirty atmospheres.
Listed by the Canadian Standards Association and CRN registered heat exchanger.
Model HC
Dimensions - Models HSB/HC
Mounting Holes:
Sizes 18-86, 3/8"-16 Tap
Sizes 108-340,1/2"-13 Tap
➀ Top/Bottom Connections (HSB only)
➁ Side Connections (HC only)
HSB HC
CD ➂
Approx.
Weight (lbs)Model Size A B A B
18 & 24 12.38 13.00 11.50 13.00 6.00 5.00 16 & 20
33 & 47 16.38 17.50 15.00 17.50 8.75 6.00 34 & 36
63 & 86 20.44 21.50 18.50 21.50 8.75 7.75 48 & 52
108 & 121 24.44 25.50 22.50 25.50 9.50 6.75 74 & 76
165 30.50 30.50 26.50 29.50 9.25 8.50 92
193 30.50 30.50 30.50 32.50 9.25 8.50 98
258 & 290 38.50 38.50 38.50 38.50 12.50 10.00 162 & 168
340 38.50 44.50 38.50 44.50 12.50 10.00 176
➂ Dimensions shown apply to standard
115V/1ph motor (Power Code 01).
Performance Data (60°F Entering Air Temperature)
➂ Dimensions shown apply to standard 115V/1ph motor (Power Code 01).
Model HSB