Table 18.1 is used to determine how water temperature drop affects heater capacity in Btu, water flow rate in GPM and pressure
drop in feet of water. These factors should be applied to the values at actual entering water and air temperature conditions.
Table 18.1
Correction Factors for Varying Water Temperature Drop
Water Temperature Drop, °F
5 10 15 20 25 30 35 40 45 50 55 60
Btu Correction Factor 1.23 1.13 1.06 1.00 0.95 0.90 0.86 0.82 0.78 0.72 0.69 0.67
GPM Correction Factor 4.64 2.21 1.40 1.00 0.76 0.61 0.50 0.42 0.36 0.30 0.26 0.23
WPD Correction Factor 17.24 4.32 1.85 1.00 0.61 0.41 0.30 0.22 0.18 0.14 0.12 0.11



Btu
A
= Btu
S
x Btu Correction Factor
GPM
A
= GPM
S
x GPM Correction Factor
WPD
A
= WPD
S
x WPD Correction Factor

Btu
S
= Btu
A
÷ Btu Correction Factor
Where:
Btu
S

through 20.2
Btu
A

GPM
S

through 20.2
GPM
A

WPD
S

Tables 19.1 through 20.2
WPD
A

Other miscellaneous useful formulas:
FAT
A
= EAT
A
+ [(460 + EAT
A
) x (Btu
A
) ÷ (573 x Cfm
s
)] for HSB and HC units only
FAT
A
= EAT
A
+ [(460 + EAT
A
) ÷ ((573 x Cfm
s
÷ Btu
A
) - 1)] for V/VN and PT/PTN units only
WTD
A
= Btu
A
÷ (480 x GPM
A
)
Where:
EAT
A
= Entering air temperature at actual conditions
FAT
A
= Final air temperature at actual conditions
Btu
A
= Capacity at actual conditions
Cfm
S
= Unit airflow as found in Tables 19.1 through 20.2
GPM
A
= Water flow rate at actual conditions in GPM
WTD
A
= Water temperature drop at actual conditions
PERFORMANCE DATA
Hot Water Conversion Tables - Miscellaneous Formulas