PERFORMANCE DATA
Hot Water Conversion Tables - Example Calculations
Conversion factor example #1:


Solution:



The standard rated capacity of an HSB 86 is based on water flow rate of 6.3 GPM, from Table 19.1.
The standard high motor speed airflow of an HSB 86 is 1340 CFM, from Table 19.1.
The maximum mounting height, at standard conditions for an HSB 86 is 16 feet, from Table 19.1.

Btu
A
= Btu
S
x Heating Capacity Factor = 60,200 x 1.201 = 
For water flow rate, since only the entering water and air temperature conditions have changed, the water flow rate will remain
6.3 GPM.
WTD
A
= Btu
A

A

FAT
A
= EAT
A

A

A

s

Max. Mounting Height
A
= Max. Mounting Height
S
x Correction Factor = 16 ft. x 0.89 = 14.2 feet
Conversion factor example #2:

water flow rate, water temperature drop, final air temperature and maximum mounting height?
Solution:



Btu
S
= Btu
A

From Table 19.1, a V 279
The capacity of the V 279 at actual conditions will be Btu
A
= Btu
S
x Heating Capacity Factor = 212,600 x 0.714 =

Since the capacity was calculated based off standard conditions with factors for changes in entering water and air temperature
conditions, the water flow rate will remain 22.2 GPM.
WTD
A
= Btu
A

A

FAT
A
= EAT
A

A

s
÷ Btu
A

Max. Mounting Height
A
= Max. Mounting Height
S
47.6 feet