User Guide

Infrared Heater Selection Procedure – General
9-200.6 5
Table 5.1 – High Intensity Minimum Clearances to
Combustibles (inches)
Model Sizes
30
60
90
130
160
SIDE OF HEATER
30 32 48 48 50
BACK OF HEATER
18 18 30 30 32
TOP OF HEATER:
28 40 42 52 60
BELOW HEATER:
- Standard Reflector 72 72 98 120 132
- w/Optional Parabolic
Reflector
72 80 98 120 132
Refer to the figures below.
Figure 5.1 – High Intensity Clearance to Combustibles
Figure 5.2 – Clearance to Stored/Stacked Materials
Table 5.2 – Low Intensity Clearance to Combustibles
Model
Series
Model Size
(MBH)
A B C
IPT
50/60 9 54 20
75/100/125 9 76 24
150/175/200 12 106 38
Clearance to each end and above the U-Tube is 12 inches.
Refer to the figures below.
Figure 5.3 – Low Intensity Clearance to Combustibles
Straight Tube Systems
Figure 5.4 – Low Intensity Clearance to Combustibles U-
Tube Systems and U-Tube
12”
12”