User Manual
19
6-580.10
Table 19.2 - Propeller Unit Model PDP Operating Electrical Data ➂
Model Number
PDP 150 PDP 175 PDP 200 PDP 250 PDP 300 PDP 350 PDP 400 BDP 150 BDP 175 BDP 200 BDP 250 BDP 300 BDP 350 BDP 400
Btu/Hr. Input
➀ 150,000 175,000 200,000 250,000 300,000 350,000 400,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr. Output
➀ 120,000 140,000 160,000 200,000 240,000 280,000 320,000 120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow (CFM)
2180 2550 2870 3700 4460 4870 5440 2020 2357 2694 3367 4040 4714 5387
CFM Range – – – – – – – 1587-2778 1852-3241 2116-3704 2646-4630 3175-5556 3704-6481 4233-6584
Air Temp. Rise (°F) 51 51 52 50 50 53 54 40-70 40-70 40-70 40-70 40-70 40-70 40-70
Max. Mounting Hgt.
(Ft.) ➁ 16 17 15 19 21 20 19 14 15 13 16 18 19 19
Heat Throw (Ft)
➁
(Max. Mtg. Hgt.) 55 59 51 67 74 70 69 49 52 47 58 64 67 68
Motor Type
➂
PSC PSC PSC PSC PSC PSC PSC
115/60/1 (PC01) 1/8 1/6 1/6 1/3 1/2 3/4 3/4
230/60/1 (PC02) 1/8 1/6 1/6 1/3 1/2 3/4 3/4
208/60/1 (PC03)
N/A 1/6 1/6 N/A N/A N/A N/A
Supply
Voltage
Power Code
Model PDP Sizes
150 175 200 250 300 350 400
115V
1 Phase
01 (115V)
Motor Amps 2.30 2.80 2.80 5.40 7.50 8.80 8.80
Total Amps 4.05 4.55 5.15 7.75 9.85 11.15 11.15
Transformer kVA n/a n/a n/a n/a n/a n/a n/a
208V
1 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 1.00 1.00 1.00 1.50 1.50 1.50
208V Total Amps 2.24 2.52 2.85 4.28 5.45 6.16 6.16
03 (208V)
Motor Amps
n/a
1.00 1.00
n/a n/a n/a n/a
Total Amps 1.90 2.15
230V
1 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.75 0.75 1.00 1.50 1.50 1.50
230V Total Amps 2.03 2.28 2.58 3.88 4.93 5.58 5.58
02 (230V)
Motor Amps 0.80 1.00 1.00 2.20 2.30 4.40 4.40
Total Amps 1.64 1.84 2.28 3.48 3.58 5.68 5.68
208V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 1.00 1.00 1.00 1.50 1.50 1.50
208V Total Amps 2.24 2.52 2.85 4.28 5.45 6.16 6.16
230V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.75 0.75 1.00 1.50 1.50 1.50
230V Total Amps 2.03 2.28 2.58 3.88 4.93 5.58 5.58
460V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.75 0.75 1.00 1.50 1.50 1.50
460V Total Amps 1.01 1.14 1.29 1.94 2.46 2.79 2.79
575V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.75 0.75 1.00 1.50 1.50 1.50
575V Total Amps 0.81 0.91 1.03 1.55 1.97 2.23 2.23
Table 19.1 - Performance - Propeller (PDP) and Blower (BDP) Models
➀ ➁
GENERAL PERFORMANCE DATA
HP
For motor size details, refer to pages 20 and 21.
Table 19.3 - Blower Model BDP Motor Amp Draw - ➃ ➄
Motor HP
Supply Voltage
115V/1ph 230V/1ph 208V/3ph 230V/3ph 460V/3ph 575V/3ph
1/4
3.70 2.70 1.40 1.50 0.75 0.46
1/3
5.00 2.50 1.10 1.10 0.60 0.64
1/2
7.20 3.60 2.10 2.20 1.10 0.80
3/4
11.00 5.50 3.00 3.00 1.50 1.30
1
14.00 7.00 3.20 3.20 1.60 1.30
1-1/2
15.00 7.50 4.60 4.80 2.40 1.90
2
- - 6.00 5.80 2.90 2.30
3
- - 8.40 7.80 3.90 3.20
5
- - 13.60 12.30 6.20 5.10
Model Size
Supply Voltage
115V/1ph 230V/1ph 208V/3ph 230V/3ph 460V/3ph 575V/3ph
150-175 1.75 0.84 0.86 0.84 0.42 0.44
200-400 2.35 1.28 1.10 1.28 0.72 0.62
Table 19.4 - Blower Model BDP Control Circuit Amp Draw ➃ ➄
Model Size
Supply Voltage
208V
1 or 3 ph
230V
1 or 3 ph
460V
3 ph
575V
3 ph
150-175 n/a n/a 0.25 0.25
200-400 n/a n/a 0.50 0.50
Table 19.5 - Blower Model BDP
Accessory Transformer Size (kVA) ➅
Ratings shown are for elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (In Canada see rating
plate.) Reduction of ratings requires use of a high altitude kit.
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor manufacturer and
Modine. Model BDP motors are totally enclosed and all single phase motors have built-in thermal overload protection.
➃ Amp draw data shown is operating amp draw at incoming power. For units that use a field installed accessory step-down transformer as noted, the amp draw shown is the primary side
operating amp draw. For sizing of circuit protection for equipment with transformers, please refer to the National Electric Code.
➄ For BDP models, add the Motor Amp Draw and Control Circuit Amp Draw to get the Total Unit Amp Draw.
➅ Transformers for blower models are typically smaller than those used for propeller models, as the transformer is not needed for the blower motor.