Brochure

10
6-170.9
ELECTRICAL SELECTION DETAILS - ALL MODELS
Table 10.1 - Electrical Selection Details - All Models
Model
Supply
Voltage
Phase
Motor
Voltage
Required Accessory
Transformer
Power & Gas Control Circuit
Transformer Voltages
Factory Installed
Transformer
Motor Starter
Coil Voltage
PTC
115 1
115V/1ph
none
115V/1ph 115 to 24V none
208
1 or 3
208V to 115V
230 230V to 115V
460
3
460V to 115V
575 575V to 115V
BTC
115 1 115V/1ph none
115V/1ph 115 to 24V
none
208
1
208V/1ph 208V to 115V
115V
230 230V/1ph 230V to 115V
208
3
208V/3ph 208V to 115V
230 230V/3ph 230V to 115V
460
3
460V/3ph 460V to 115V
575 575V/3ph 575V to 115V
For accessory transformer sizing, refer to Table 5.2 for model PTC and Table 6.4 for model BTC.
Table 10.2 - Gas Controls – All Models
Model
Size Control System Description
Gas
Type
Control
Code
Control
Voltage
55-310
Single-Stage, Direct Spark Ignition
Utilizes a single-stage combination gas control and an ignition control.
Gas is automatically lit with the direct spark igniter on call for heat.
Natural 11
24V
Propane 21
All ignition controls are 100% Shut-Off with Continuous Retry.