Use and Care Manual

16
6-560.8
BLOWER PERFORMANCE DATA - MODEL BTP
Table 16.1 - Power Code Description - Blower Model BTP -
Table 16.2 - Filter Static Pressure Drop
BTP150 BTP175 BTP200 BTP250 BTP300 BTP350 BTP400
Filter Static ("W.C.) 0.1 0.2 0.1 0.2 0.2 0.2 0.2
Forblowerunitswithenclosureandlter,addthefollowingstaticpressurestothestaticpressuredeterminedbythesystemdesignerfortotal
external static pressure.
Power
Code
Voltage Phase
BTP150 BTP175 BTP200 BTP250 BTP300 BTP350 BTP400
HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
01
115 1 1/4 230 - - - - - - - - - - - -
02
115/230 1 1/3 230 1/3 238 1/2 233 1/2 204 1 240 1 1/2 250 1 1/2 247
08
208-230/460 3 1/3 230 1/3 238 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
11
575 3 1/3 231 1/3 239 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
13
115/230 1 1/3 232 1/2 229 1 229 1 241 1 241 1 1/2 247 - -
19
208-230/460 3 1/3 232 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
22
575 3 1/3 233 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
24
115/230 1 1/2 229 1 175 1 175 1.5 23 1 1/2 243 1 1/2 252 - -
30
208-230/460 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
33
575 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
35
115/230 1 1 175 1 1/2 237 1 1/2 235 - - 1 1/2 23 - - - -
41
208-230/460 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
44
575 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
52
208-230/460 3 - - - - - - - - 2 177 2 180 - -
55
575 3 - - - - - - - - 2 177 2 180 - -
63
208-230/460 3 - - - - - - - - 3 112 3 246 - -
66
575 3 - - - - - - - - 3 112 3 246 - -
74
208-230/460 3 - - - - - - - - - - 5 245 - -
77
575 3 - - - - - - - - - - 5 245 - -
For selection of correct power code, refer to the tables on pages 17-18.