Submittal Data Sheet

AccuSpec V4.24ha
GENERAL PERFORMANCE DATA
General Performance Data
Model PTC 85
At 0’ Elevation
Btu/Hr. Input 85,000
Btu/Hr. Output 79,050
Entering Airflow (CFM) 1650
Outlet Velocity 619
Air Temp. Rise (°F) 44
Mounting Height (Max Ft.)
1
13
Heat Throw (Max. Mtg. Ft.)
2
48
Unit Total Power (Amps) 4.35
Condensate Produced (gal/hr) 0.5
As Configured at 0-2000 Ft. Elevation
Btu/Hr. Input 85,000
Btu/Hr. Output 79,050
Configured Air Temp Rise (°F) 44
Motor Data
Horse Power 1/8
RPM 1625
Type P.S.C.
Motor Amps at 115V 2.20
Clearances to Combustibles
Top and Bottom 6”
Vent/Combustion Air Connector 6”
Access Side 6”
Non-Access Side 6”
Rear 18”
1
At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit.
2
Heat Throws are calculated at 65°F ambient with a 44°F air temperature rise with the unit mounted at a maximum mounting
height of 13 feet.