Submittal Data Sheet

AccuSpec V4.24ha
GENERAL PERFORMANCE DATA
General Performance Data
Model PTC 310
At 0’ Elevation
Btu/Hr. Input 310,000
Btu/Hr. Output 288,300
Entering Airflow (CFM) 5400
Outlet Velocity 765
Air Temp. Rise (°F) 49
Mounting Height (Max Ft.)
1
19
Heat Throw (Max. Mtg. Ft.)
2
67
Unit Total Power (Amps) 9.85
Condensate Produced (gal/hr) 2.3
As Configured at 0-2000 Ft. Elevation
Btu/Hr. Input 310,000
Btu/Hr. Output 288,300
Configured Air Temp Rise (°F) 49
Motor Data
Horse Power 3/4
RPM 1125
Type P.S.C.
Motor Amps at 115V 8.80
Clearances to Combustibles
Top and Bottom 6”
Vent/Combustion Air Connector 6”
Access Side 6”
Non-Access Side 6”
Rear 18”
1
At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit.
2
Heat Throws are calculated at 65°F ambient with a 49°F air temperature rise with the unit mounted at a maximum mounting
height of 19 feet.