17
6-561.10
BLOWER PERFORMANCE DATA - MODEL BTS
Table 17.1 - Power Code Description - Blower Model BTS -
Table 17.2 - Filter Static Pressure Drop
BTS150 BTS175 BTS200 BTS250 BTS300 BTS350 BTS400
Filter Static ("W.C.) 0.1 0.2 0.1 0.2 0.2 0.2 0.2
Forblowerunitswithenclosureandlter,addthefollowingstaticpressurestothestaticpressuredeterminedbythesystemdesignerfortotal
external static pressure.
Power
Code
Voltage Phase
BTS150 BTS175 BTS200 BTS250 BTS300 BTS350 BTS400
HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
01
115 1 1/4 230 - - - - - - - - - - - -
02
115/230 1 1/3 230 1/3 238 1/2 233 1/2 204 1 240 1 1/2 250 1 1/2 247
08
208-230/460 3 1/3 230 1/3 238 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
11
575 3 1/3 231 1/3 239 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
13
115/230 1 1/3 232 1/2 229 1 229 1 241 1 241 1 1/2 247 - -
19
208-230/460 3 1/3 232 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
22
575 3 1/3 233 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
24
115/230 1 1/2 229 1 175 1 175 1.5 23 1 1/2 243 1 1/2 252 - -
30
208-230/460 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
33
575 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
35
115/230 1 1 175 1 1/2 237 1 1/2 235 - - 1 1/2 23 - - - -
41
208-230/460 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
44
575 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
52
208-230/460 3 - - - - - - - - 2 177 2 180 - -
55
575 3 - - - - - - - - 2 177 2 180 - -
63
208-230/460 3 - - - - - - - - 3 112 3 246 - -
66
575 3 - - - - - - - - 3 112 3 246 - -
74
208-230/460 3 - - - - - - - - - - 5 245 - -
77
575 3 - - - - - - - - - - 5 245 - -
For selection of correct power code, refer to the tables on pages 18-19.