VN385S01 Installation and Service Manual

1-550.26
8
2
lbs.
STEAM
60° ENT. AIR
Table 8.1
Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
High Motor Speed
Air Data Motor Data
Maximum Heat Throw Final
Sound Mounting or Spread Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18 18,000 75 II 8 17 340 625 107 19 1/60 1550
HSB/HC-24 24,000 100 II 9 18 370 695 119 25 1/25 1550
HSB/HC-33 33,000 138 II 10 21 630 690 108 34 1/25 1550
HSB/HC-47 47,000 196 III 12 28 730 810 119 49 1/12 1550
HSB/HC-63 63,000 263 III 14 29 1120 690 111 65 1/12 1550
HSB/HC-86 86,000 358 III 15 31 1340 835 118 89 1/8 1625
Horizontal HSB/HC-108 108,000 450 III 17 31 2010 790 109 112 1/8 1625
Delivery HSB/HC-121 121,000 504 III 16 25 1775 715 122 125 1/5 1075
HSB/HC-165 165,000 688 IV 19 40 3240 880 106 171 1/3 1075
HSB/HC-193 193,000 804 IV 18 38 2900 810 121 200 1/3 1075
HSB/HC-258 258,000 1075 V 19 44 4560 750 111 267 1/2 1075
HSB/HC-290 290,000 1208 V 20 46 4590 765 117 300 1/2 1075
HSB/HC-340 340,000 1417 V 20 46 5130 735 120 352 1/2 1075
PT/PTN-279 279,000 1163 V 16 100 5460 2165 111 289 1/2 1075
PT/PTN-333 333,000 1388 VI 17 110 5980 2165 116 345 3/4 1140
Power PT/PTN-385 385,000 1604 VI 17 115 7680 1860 110 398 1 1140
Throw
PT/PTN-500 500,000 2083 VI 18 130 10,390 2520 108 517 1-1/2 1140
PT/PTN-610 610,000 2542 VI 20 140 11,750 2315 112 631 1-1/2 1140
PT-952 952,000 3967 VI 21 145 12,170 2321 139 985 2 1140
V/VN-42 42,000 175 II 11 15 17 11 950 825 103 43 1/30 1050
V/VN-59 59,000 246 II 14 19 21 14 1155 1005 111 61 1/30 1050
V/VN-78 78,000 325 II 15 20 23 15 1590 1065 109 81 1/15 1050
V/VN-95 95,000 396 II 15 20 23 15 1665 1120 118 98 1/15 1050
Vertical V/VN-139 139,000 579 III 18 24 27 18 2660 1285 112 144 1/6 1075
Delivery V/VN-161 161,000 671 IV 20 27 30 20 2945 1420 115 167 1/3 1075
V/VN-193 193,000 804 IV 22 30 33 22 3500 1690 116 200 1/3 1075
V/VN-212 212,000 883 IV 22 30 33 22 3610 1740 120 219 1/3 1075
V/VN-247 247,000 1029 V 26 34 39 26 4820 1910 111 256 1/2 1075
V/VN-279 279,000 1163 V 30 37 45 30 5460 2165 111 289 1 /2 1075
V/VN-333 333,000 1388 V 30 37 45 30 5980 2165 116 345 3/4 1140
V/VN-385 385,000 1604 VI 30 36 45 30 7680 1860 110 398 1 1140
V/VN-500 500,000 2083 VI 37 44 56 37 10,390 2520 108 517 1-1/2 1140
V/VN-610 610,000 2542 VI 36 43 54 36 11,750 2315 112 631 1-1/2 1140
V-952 952,000 3967 VI 37 45 56 56 12,170 2321 139 985 2 1140
Table 8.2
Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
Reduced Motor Speed
Air Data Motor Data
Maximum Final
Sound Mounting Heat Throw Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18 14,000 58 I 8 10 220 415 118 14 1/60 1000
HSB/HC-24 18,000 75 I 9 11 230 440 131 19 1/25 1000
HSB/HC-33 25,000 104 I 10 13 395 440 118 26 1/25 1000
Horizontal HSB/HC-47 38,000 158 II 12 17 450 515 137 39 1/12 1000
Delivery HSB/HC-63 47,000 195 II 14 17 685 430 122 49 1/12 1000
HSB/HC-86 64,000 265 II 15 19 825 525 131 66 1/8 1000
HSB/HC-108 81,000 340 II 17 19 1255 500 119 84 1/8 1000
STEAM PERFORMANCE DATA - STANDARD MODELS
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
CFM for horizontal types is entering CFM. CFM for vertical and Power Throw
types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes.
Requires Solid State Motor Speed Controller.