Table 8.1
Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
High Motor Speed
Air Data Motor Data
Maximum Heat Throw Final
Sound Mounting or Spread Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR ➃ Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18 18,000 75 II 8 17 340 625 107 19 1/60 1550
HSB/HC-24 24,000 100 II 9 18 370 695 119 25 1/25 1550
HSB/HC-33 33,000 138 II 10 21 630 690 108 34 1/25 1550
HSB/HC-47 47,000 196 III 12 28 730 810 119 49 1/12 1550
HSB/HC-63 63,000 263 III 14 29 1120 690 111 65 1/12 1550
HSB/HC-86 86,000 358 III 15 31 1340 835 118 89 1/8 1625
Horizontal HSB/HC-108 108,000 450 III 17 31 2010 790 109 112 1/8 1625
Delivery HSB/HC-121 121,000 504 III 16 25 1775 715 122 125 1/5 1075
HSB/HC-165 165,000 688 IV 19 40 3240 880 106 171 1/3 1075
HSB/HC-193 193,000 804 IV 18 38 2900 810 121 200 1/3 1075
HSB/HC-258 258,000 1075 V 19 44 4560 750 111 267 1/2 1075
HSB/HC-290 290,000 1208 V 20 46 4590 765 117 300 1/2 1075
HSB/HC-340 340,000 1417 V 20 46 5130 735 120 352 1/2 1075
PT/PTN-279 279,000 1163 V 16 100 5460 2165 111 289 1/2 1075
PT/PTN-333 333,000 1388 VI 17 110 5980 2165 116 345 3/4 1140
Power PT/PTN-385 385,000 1604 VI 17 115 7680 1860 110 398 1 1140
Throw
™
PT/PTN-500 500,000 2083 VI 18 130 10,390 2520 108 517 1-1/2 1140
➂ PT/PTN-610 610,000 2542 VI 20 140 11,750 2315 112 631 1-1/2 1140
PT-952 952,000 3967 VI 21 145 12,170 2321 139 985 2 1140
V/VN-42 42,000 175 II 11 15 17 11 950 825 103 43 1/30 1050
V/VN-59 59,000 246 II 14 19 21 14 1155 1005 111 61 1/30 1050
V/VN-78 78,000 325 II 15 20 23 15 1590 1065 109 81 1/15 1050
V/VN-95 95,000 396 II 15 20 23 15 1665 1120 118 98 1/15 1050
Vertical V/VN-139 139,000 579 III 18 24 27 18 2660 1285 112 144 1/6 1075
Delivery V/VN-161 161,000 671 IV 20 27 30 20 2945 1420 115 167 1/3 1075
V/VN-193 193,000 804 IV 22 30 33 22 3500 1690 116 200 1/3 1075
V/VN-212 212,000 883 IV 22 30 33 22 3610 1740 120 219 1/3 1075
V/VN-247 247,000 1029 V 26 34 39 26 4820 1910 111 256 1/2 1075
V/VN-279 279,000 1163 V 30 37 45 30 5460 2165 111 289 1 /2 1075
V/VN-333 333,000 1388 V 30 37 45 30 5980 2165 116 345 3/4 1140
V/VN-385 385,000 1604 VI 30 36 45 30 7680 1860 110 398 1 1140
V/VN-500 500,000 2083 VI 37 44 56 37 10,390 2520 108 517 1-1/2 1140
V/VN-610 610,000 2542 VI 36 43 54 36 11,750 2315 112 631 1-1/2 1140
V-952 952,000 3967 VI 37 45 56 56 12,170 2321 139 985 2 1140
Table 8.2
Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
Reduced Motor Speed ➃
Air Data Motor Data
Maximum Final
Sound Mounting Heat Throw Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR ➃ Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18 14,000 58 I 8 10 220 415 118 14 1/60 1000
HSB/HC-24 18,000 75 I 9 11 230 440 131 19 1/25 1000
HSB/HC-33 25,000 104 I 10 13 395 440 118 26 1/25 1000
Horizontal HSB/HC-47 38,000 158 II 12 17 450 515 137 39 1/12 1000
Delivery HSB/HC-63 47,000 195 II 14 17 685 430 122 49 1/12 1000
HSB/HC-86 64,000 265 II 15 19 825 525 131 66 1/8 1000
HSB/HC-108 81,000 340 II 17 19 1255 500 119 84 1/8 1000
STEAM PERFORMANCE DATA - STANDARD MODELS
➀ Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
➁ CFM for horizontal types is entering CFM. CFM for vertical and Power Throw
™
types is leaving CFM.
➂ V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes.
➃ Requires Solid State Motor Speed Controller.