200°F ENTERING
WATER
60°F ENTERING
AIR
20°F WATER
TEMPERATURE
DROP
Table 10.1
Performance Data for Standard Units at Standard Conditions of 200°F Entering Water and 60°F
Entering Air High Motor Speed
Water Data Air Data Motor Data
Pressure Maximum Heat Throw
Drop Sound Mounting or Spread Outlet Final Air
Model (Ft. of Min/Max Class Height @ Max. Velocity Temp. Approx.
Type No. Btu/hr. GPM Water) GPM (ft.) Height CFM (Fpm) (°F) Hp RPM
HSB/HC-18 12,600 1.3 0.5 0.3 / 5.0 II 9 18 340 615 93 1/60 1550
HSB/HC-24 16,200 1.7 0.8 0.3 / 5.0 II 10 19 370 675 100 1/25 1550
HSB/HC-33 21,700 2.3 0.2 0.4 / 10.0 II 11 23 630 675 91 1/25 1550
HSB/HC-47 30,900 3.2 0.4 0.4 / 10.0 III 13 30 730 785 98 1/12 1550
HSB/HC-63 45,600 4.7 0.6 0.5 / 20.0 III 15 31 1120 680 97 1/12 1550
Horizontal HSB/HC-86 60,200 6.3 1.0 0.5 / 20.0 III 16 33 1340 820 101 1/8 1625
Delivery HSB/HC-108 83,700 8.7 2.8 0.5 / 30.0 III 18 33 2010 775 98 1/8 1625
HSB/HC-121 93,000 9.7 3.3 0.7 / 30.0 III 17 27 1775 700 107 1/5 1075
HSB/HC-165 130,900 13.6 8.6 2.0 / 30.0 IV 20 43 3240 870 96 1/3 1075
HSB/HC-193 143,000 14.9 1.4 2.0 / 50.0 IV 19 41 2900 790 105 1/3 1075
HSB/HC-258 201,900 21.0 5.7 2.5 / 70.0 V 20 47 4560 740 100 1/2 1075
HSB/HC-290 228,600 23.8 7.1 2.5 / 70.0 V 22 50 4590 750 105 1/2 1075
HSB/HC-340 271,100 28.2 11.3 2.8 / 70.0 V 22 50 5130 720 108 1/2 1075
PT/PTN-279 192,300 20.0 0.2 4.5 / 60.0 V 17 108 5460 2165 94 1/2 1075
PT/PTN-333 238,500 24.8 0.4 4.5 / 100.0 VI 18 117 5980 2165 99 3/4 1140
Power PT/PTN-385 276,100 28.8 0.6 4.5 / 100.0 VI 18 124 7680 1860 95 1 1140
Throw
PT/PTN-500 358,000 37.3 0.5 6.0 / 100.0 VI 19 138 10,390 2520 93 1-1/2 1140
PT/PTN-610 450,400 46.9 1.0 6.0 / 100.0 VI 22 151 11,750 2315 97 1-1/2 1140
PT-952 721,600 75.2 1.1 14.0 / 200.0 VI 23 150 12,166 2321 120 2 1140
V/VN-42 30,100 3.1 0.6 0.5 / 10.0 II 12 16 18 12 950 825 90 1/30 1050
V/VN-59 42,600 4.4 0.5 0.8 / 15.0 II 15 20 22 15 1155 1005 96 1/30 1050
V/VN-78 57,000 5.9 0.5 1.0 / 20.0 II 16 22 24 16 1590 1065 95 1/15 1050
V/VN-95 69,300 7.2 0.5 1.3 / 25.0 II 16 22 24 16 1665 1120 101 1/15 1050
V/VN-139 106,600 11.1 2.6 1.0 / 30.0 III 19 26 29 19 2660 1285 99 1/6 1075
Vertical V/VN-161 123,200 12.8 2.2 1.3 / 40.0 IV 21 29 32 22 2945 1420 101 1/3 1075
Delivery V/VN-193 147,200 15.3 2.2 1.5 / 50.0 IV 23 32 35 24 3500 1690 101 1/3 1075
V/VN-212 161,700 16.8 1.5 2.0 / 60.0 IV 23 32 35 24 3610 1740 104 1/3 1075
V/VN-247 188,700 19.7 2.1 2.0 / 60.0 V 28 37 41 28 4820 1910 98 1/2 1075
V/VN-279 212,600 22.2 2.1 2.3 / 75.0 V 32 40 48 32 5460 2165 98 1/2 1075
V/VN-333 260,100 27.1 3.8 2.8 / 75.0 V 32 40 48 32 5980 2165 102 3/4 1140
V/VN-385 302,100 31.5 5.0 3.3 / 75.0 VI 32 39 48 32 7680 1860 98 1 1140
V/VN-500 391,700 40.8 4.8 3.0 / 100.0 VI 39 47 59 40 10,390 2520 96 1-1/2 1140
V/VN-610 450,400 46.9 1.0 6.0 / 100.0 VI 38 46 57 39 11,750 2315 97 1-1/2 1140
V-952 721,600 75.2 1.1 14.0 / 200.0 VI 39 63 59 70 12,166 2321 120 2 1140
Table 10.2
Performance Data for Standard Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air
Reduced Motor Speeds
Water Data Air Data Motor Data
Pressure Maximum
Drop Sound Mounting Heat Throw Outlet Final Air
Model (Ft. of Class Height @ Max. Velocity Temp. Approx.
Type No. Btu/hr. GPM Water) (ft.) Height CFM (Fpm) (°F) Hp RPM
HSB/HC-18 9900 1.3 0.5 I 9 11 220 400 101 1/60 1000
HSB/HC-24 12,400 1.7 0.8 I 10 12 230 425 109 1/25 1000
Horizontal HSB/HC-33 16,700 2.3 0.2 I 11 14 395 430 98 1/25 1000
Delivery HSB/HC-47 23,600 3.2 0.4 II 13 18 450 490 107 1/12 1000
HSB/HC-63 34,600 4.7 0.6 II 15 18 685 420 106 1/12 1000
HSB/HC-86 45,900 6.3 1.0 II 16 20 825 515 110 1/8 1000
HSB/HC-108 64,300 8.7 2.8 II 18 20 1255 490 106 1/8 1000
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
Non-bolded mounting height/spread data is for units without deflectors.
CFM for horizontal types is entering CFM. CFM for vertical and Power Throw
types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes.
Requires Solid State Motor Speed Controller.
HOT WATER PERFORMANCE DATA - STANDARD MODELS