Installation and Service Manual

Table 9.1
Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
High Motor Speed
Air Data Motor Data
Maximum Heat Throw Final
Sound Mounting or Spread Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18L 15,900 66 II 9 20 364 655 100 16 1/60 1550
HSB/HC-24L 19,300 80 II 11 21 435 795 100 20 1/25 1550
HSB/HC-33L 29,500 123 II 12 24 695 745 99 31 1/25 1550
HSB/HC-47L 32,000 133 III 14 32 855 910 94 33 1/12 1550
HSB/HC-63L 52,500 219 III 16 33 1170 710 101 54 1/12 1550
Horizontal HSB/HC-86L 61,500 256 III 17 36 1510 910 97 64 1/8 1625
Delivery HSB/HC-108L 86,500 360 III 19 36 2150 825 97 90 1/8 1625
HSB/HC-121L 88,000 367 III 18 29 2070 800 98 91 1/5 1075
HSB/HC-165L 143,000 596 IV 21 45 3480 930 97 148 1/3 1075
HSB/HC-258L 190,000 792 V 22 51 4655 750 98 197 1/2 1075
HSB/HC-290L 207,000 863 V 23 53 5040 805 94 214 1/2 1075
HSB/HC-340L 255,000 1063 V 23 53 5575 775 102 264 1/2 1075
Power PT/PTN-
Throw
610L
V/VN-42L 33,000 138 II 13 17 20 13 960 835 94 34 1/30 1050
V/VN-59L 44,000 183 II 16 22 24 16 1190 1035 96 45 1/30 1050
V/VN-78L 62,000 258 II 19 26 29 19 1740 1070 95 65 1/15 1050
V/VN-95L 71,000 296 II 19 26 29 19 1760 1180 99 73 1/15 1050
V/VN-139L 103,000 429 III 23 31 35 23 2860 1380 95 106 1/6 1075
V/VN-161L 127,000 529 IV 26 35 39 26 3400 1640 96 132 1/3 1075
Vertical V/VN-193L 149,000 621 IV 27 36 41 27 3710 1790 99 154 1/3 1075
Delivery V/VN-212L 163,000 679 IV 27 36 41 27 3830 1845 102 169 1/3 1075
V/VN-247L 190,000 792 V 32 42 48 32 5110 2030 96 197 1/2 1075
V/VN-279L 215,000 896 V 36 45 54 36 5790 2300 96 222 1/2 1075
V/VN-333L 256,000 1067 V 36 45 54 36 6340 2300 100 265 3/4 1140
V/VN-385L 296,000 1233 VI 36 43 54 36 8140 1970 95 307 1 1140
V/VN-500L 385,000 1604 VI 45 54 68 45 11,000 2670 94 400 1-1/2 1140
V/VN-610L 470,000 1958 VI 44 52 66 44 12,400 2445 97 485 1-1/2 1140
V-952L 733,000 3055 VI 45 61 68 68 12,940 2450 115 759 2 1140
Table 9.2
Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
Reduced Motor Speed
Air Data Motor Data
Maximum Final
Sound Mounting Heat Throw Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18L 12,000 51 I 9 12 230 425 108 12 1/60 1000
HSB/HC-24L 14,400 60 1 11 13 265 490 109 15 1/25 1000
Horizontal HSB/HC-33L 22,000 92 I 12 14 430 470 107 23 1/25 1000
Delivery HSB/HC-47L 24,300 101 II 14 19 540 580 101 25 1/12 1000
HSB/HC-63L 39,500 164 II 16 20 725 445 109 41 1/12 1000
HSB/HC-86L 46,000 192 II 17 22 925 565 105 48 1/8 1000
HSB/HC-108L 65,000 270 II 19 22 1330 520 104 67 1/8 1000
9
2
lbs.
STEAM
60° ENT. AIR
470,000 1958 VI 22 154 2400 2445 97 486 1-1/2 1140
STEAM PERFORMANCE DATA - LOW OUTLET TEMPERATURE MODELS
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
CFM for horizontal types is entering CFM. CFM for vertical and Power Throw
TM
types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes.
Requires Solid State Motor Speed Controller.
1-550.26