Installation and Service Manual
Table 9.1
Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
High Motor Speed
Air Data Motor Data
Maximum Heat Throw Final
Sound Mounting or Spread Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR ➃ Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18L 15,900 66 II 9 20 364 655 100 16 1/60 1550
HSB/HC-24L 19,300 80 II 11 21 435 795 100 20 1/25 1550
HSB/HC-33L 29,500 123 II 12 24 695 745 99 31 1/25 1550
HSB/HC-47L 32,000 133 III 14 32 855 910 94 33 1/12 1550
HSB/HC-63L 52,500 219 III 16 33 1170 710 101 54 1/12 1550
Horizontal HSB/HC-86L 61,500 256 III 17 36 1510 910 97 64 1/8 1625
Delivery HSB/HC-108L 86,500 360 III 19 36 2150 825 97 90 1/8 1625
➂ HSB/HC-121L 88,000 367 III 18 29 2070 800 98 91 1/5 1075
HSB/HC-165L 143,000 596 IV 21 45 3480 930 97 148 1/3 1075
HSB/HC-258L 190,000 792 V 22 51 4655 750 98 197 1/2 1075
HSB/HC-290L 207,000 863 V 23 53 5040 805 94 214 1/2 1075
HSB/HC-340L 255,000 1063 V 23 53 5575 775 102 264 1/2 1075
Power PT/PTN-
Throw
™
➂ 610L
V/VN-42L 33,000 138 II 13 17 20 13 960 835 94 34 1/30 1050
V/VN-59L 44,000 183 II 16 22 24 16 1190 1035 96 45 1/30 1050
V/VN-78L 62,000 258 II 19 26 29 19 1740 1070 95 65 1/15 1050
V/VN-95L 71,000 296 II 19 26 29 19 1760 1180 99 73 1/15 1050
V/VN-139L 103,000 429 III 23 31 35 23 2860 1380 95 106 1/6 1075
V/VN-161L 127,000 529 IV 26 35 39 26 3400 1640 96 132 1/3 1075
Vertical V/VN-193L 149,000 621 IV 27 36 41 27 3710 1790 99 154 1/3 1075
Delivery V/VN-212L 163,000 679 IV 27 36 41 27 3830 1845 102 169 1/3 1075
➂ V/VN-247L 190,000 792 V 32 42 48 32 5110 2030 96 197 1/2 1075
V/VN-279L 215,000 896 V 36 45 54 36 5790 2300 96 222 1/2 1075
V/VN-333L 256,000 1067 V 36 45 54 36 6340 2300 100 265 3/4 1140
V/VN-385L 296,000 1233 VI 36 43 54 36 8140 1970 95 307 1 1140
V/VN-500L 385,000 1604 VI 45 54 68 45 11,000 2670 94 400 1-1/2 1140
V/VN-610L 470,000 1958 VI 44 52 66 44 12,400 2445 97 485 1-1/2 1140
V-952L 733,000 3055 VI 45 61 68 68 12,940 2450 115 759 2 1140
Table 9.2
Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air
Reduced Motor Speed ➃
Air Data Motor Data
Maximum Final
Sound Mounting Heat Throw Outlet Air
Model Sq. Ft. Class Height (ft.) @ Max. Velocity Temp. Condensate Approx.
Type No. Btu/hr EDR ➃ Height CFM (Fpm) (°F) lb/hr Hp RPM
HSB/HC-18L 12,000 51 I 9 12 230 425 108 12 1/60 1000
HSB/HC-24L 14,400 60 1 11 13 265 490 109 15 1/25 1000
Horizontal HSB/HC-33L 22,000 92 I 12 14 430 470 107 23 1/25 1000
Delivery HSB/HC-47L 24,300 101 II 14 19 540 580 101 25 1/12 1000
HSB/HC-63L 39,500 164 II 16 20 725 445 109 41 1/12 1000
HSB/HC-86L 46,000 192 II 17 22 925 565 105 48 1/8 1000
HSB/HC-108L 65,000 270 II 19 22 1330 520 104 67 1/8 1000
9
2
lbs.
STEAM
60° ENT. AIR
470,000 1958 VI 22 154 2400 2445 97 486 1-1/2 1140
STEAM PERFORMANCE DATA - LOW OUTLET TEMPERATURE MODELS
➀ Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
➁ CFM for horizontal types is entering CFM. CFM for vertical and Power Throw
TM
types is leaving CFM.
➂ V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes.
➃ Requires Solid State Motor Speed Controller.
1-550.26