Operating instructions
39D3200
13
HEAT RESISTANT REQUIREMENTS FOR SAFE INSTALLATION WITH WOODEN MANTEL,
MATERIAL SHELF OR OTHER COMBUSTIBLE PROJECTION
MEASUREMENT
20" or more Hood not required. Observe profiles (side elevations) shown in
Figure 8.
8" to less than 12" Install hood and observe profiles shown in Figure 7; OR extend heat resistant material to at
least 12" and observe profiles shown in
Figure 8.
Less than 8" Extend heat resistant material to at least 8", install hood and observe profiles shown in
Figure 7; OR extend heat resistant material to at least 12" and observe profiles shown in
Figure 8.
CLEARANCES AND HEIGHT REQUIRMENTS
TABLE B - Heat Resistant Material Heights and Mantel Location
Heater in
Fireplace or
Firebox
Heat
Resistant
Material
10" or less
20" min. 32"
Heater in
Fireplace or
Firebox
Heat
Resistant
Material
Hood
12"
6" - 10 "
2
1
/
2
"
8"min. 13" 18" 20"
Figure 8 - Minimum Mantel Clearance
with No Hood
Figure 7 - Minimum Mantel Clearance
with Hood
Example:
The bottom of the mantel may project from
the wall a maximum of 10" at a minimum of
32" above the opening.
Example:
A mantel may project from the wall a maximum
of 2
1
/2" at a minimum of 13" above the open-
ing and a maximum of 10" at a minimum of
18" above the opening.