Owner's Manual
71D0530
8
GCUF Vent-Free Fireboxes
Ensure that minimum clearances shown in Figures 4
through 8 are maintained. Left and right clearances are
determined when facing the front of the rebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
re hazard.
1. The clearance from the inside
of the appliance to any combustible wall should not be
less than 9". Figure 4
. The ceiling must be at least 4”
from the top of the rebox opening. Figure 4
3. The appliance may be placed
against a combustible back wall.
9"
Minimum
42"
Minimum
9"
Minimum
FP2687
minimum clearances
FP687
Figure 4 -
Clearance and Height Requirements
4. The canopy supplied with the unit
must be installed. If a combustible mantel is installed,
it must meet the clearance requirements as shown in
Figure 5. However, if lower mantel height is desired,
refer to Page 14, Figure 6.
12”
10”
8”
6”
256O”
12”
16”
19”
21”
23”
FP2690
Mantel clearances
Combustible
Material Can
Contact Top
of Fireplace
FP690
Noncombustible Material
Only if Needed to Cover
Radiant Top Face
Figure 5 -
Mantel Clearances
12”
8”
8”
14”
FP2691
mantel clear wide canopy
FP691
Figure 6 -
Mantel Heights for Wide Prole Canopy
45°
1”
256O”
3”
5”
6”
56O”
56O”
56O”
FP2692
mantel leg clearance
6”
756O”
756O”
9”
Finish Wall
Combustible
Material Area
FP69
Figure 5a -
Mantel Leg Clearance