Gas Log Set Installation
7
NBST27 Unvented Gas Log Set
Monessen • NBST27 Gas Log Set Installation/Owner's Manual • 81D3032 • Rev A • 08/16
CLEARANCE AND HEIGHT REQUIREMENTS
Sidewall and ceiling clearances: The sides ofthere-
place opening must be at least 1
3
⁄4" from any combustible
wall. The ceiling must be at least 42" from the top of the
replaceopening.Thewallparalleltothesideoftheheater
must be at least 36" from the side of the heater. Refer to
yourreboxownersmanualformoreinformation.
42”
36”
36”
1³⁄₄”
FP2363
clearances
Figure 3 -
Sidewall and Ceiling Clearances
IMPORTANT:
1. If installing unit into an unvented rebox, minimum
required clearances listed in the rebox installation
manual must be met.
2. If installing unit into a vented rebox with a working
damper, minimum clearances shown in Figure 8 through
10 must be met
3. Ifinstallingunitintoaventedreboxwithadamperthat
is always open, no minimum clearances are required.
Heat resistant material (minimum requirements) with
no wooden mantel or other combustible projection:
To install the gas logs into a replace with no wooden
mantel, shelf or other combustible projection above the
replace opening, measure the heat resistant material
height, per Figure 4, then see TABLE A.
Heat resistant materials such as slate and marble must be
at least 1/2" thick. Sheet metal should not be installed
onto combustible material.
IMPORTANT: Iftheunitisinstalledinaventedreplace
and cannot meet these minimum clearances you must
operatetheheaterwithchimneyuedamperopen.Refer
to “Installing Vented Applications” on Page 11.
FP2364
Heat resist matl
Measure this Distance
Heat Resistant
Material
Heater in Fireplace or
Firebox
Figure 4 -
Measure Heat Resistant Material
Table A — Heat Resistant Material Requirements
with no Mantel or Combustible Projection
The dimensions shown in Figures 3 through 9 and
dened in the replace manufacturer's instructions
are minimum clearances to maintain when installing
this heater. Left and right clearances are determined
when facing the front of the heater.
When heater is installed into a ventless rebox,
minimum clearances, as specied by the ventless
rebox manufacturer, must be met.
Follow these instructions carefully to ensure safe
installation. Failure to follow instructions exactly
can create a re hazard.
WARNING
Heat Resistant
Material Mea-
surement Requirements for Safe Installation
12" or more Hood not required
8" to less than 12" Extend heat resistant material to 12" or
install hood. Figure 4
Less than 8" Extend heat resistant material to at
least 8" and install hood. Figure 4 OR
extend heat resistant material to a
height of at least 12"