SIPART PS2 SIPART PS2 PA 6DR400x-xx 6DR410x-xx Electropneumatic Positioner for Linear and Rotary Actuators Manual Order No.
SIPART, SITRANS, SIMATIC are Siemens registered trademarks. All other product or system names are (registered) trademarks of their respective owners and must be treated accordingly. The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights created by the granting of patents or registration of a design are reserved. Technical data subject to change without notice.
Contents 0 1 2 Information for the Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-1 0.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-1 0.2 Warning notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-2 0.3 Qualified personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-3 0.
3 Preparing for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.1 Instrument identification (type code) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.2 Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3.3 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3.3.
Information for the Operator 0 Information for the Operator Dear customer, Before you start work, please read this manual! It contains important information and data that you must observe to ensure the availability of the device and save yourself service costs. This will make it considerably easier to use this control equipment and lead to reliable results.
Information for the Operator The documentation supplied with the instrument is listed in Section 0.5. This manual is not a permanent part of the scope of supply. For reasons of clarity, it does not contain every detail about every version of the product described and cannot take every eventuality in installation, operation, maintenance and use in systems into account.
Information for the Operator ☞ Note indicates important information about the product itself or the respective part of the instruction manual which it is essential to highlight. 0.3 Qualified personnel The result of unqualified intervention in the instrument or nonobservance of the warnings given in this manual or on product labels can be severe personal injury and/or serious material damage. Therefore only properly qualified personnel must make changes and settings in the instrument.
Information for the Operator 0.4 Use as intended Use as intended for the purpose of this manual means that this product must only be used for the applications described in the technical description (see also Section 3 of this manual). The product described in this manual has been developed, manufactured, tested and documented observing the relevant safety standards.
Information for the Operator 0.7 Information about delivery The scope of delivery is listed on the dispatch papers accompanying the delivery in accordance with the valid contract of sale. When you open the packaging please observe the information on the packaging. Check that the delivery is complete and undamaged. If possible, compare the order number on the rating plates with the ordering data. For the supply range please see Section 7. 0.
Information for the Operator 0-6 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Introduction 1 Introduction 1.1 General information about the device The SIPART PS2 positioner is used to position and control pneumatic actuators. The instrument operates electropneumatically, compressed air is used as the auxiliary power. SIPART PS2 PA In the SIPART PS2 PA version, the positioner is used as a component in a digital process automation system. It communicates with the master as a slave via the PROFIBUS PS field bus.
Introduction Housing The electronics including the display and the position feedback and the valve manifold are integrated in the housing. The housing is available in two variations: ❑ Plastic housing for double-acting actuators ❑ Metal housing for single-acting actuators Degree of protection The instrument has degree of protection IP65. Explosion protection The intrinsically safe version can be operated in hazard area zone 1 or zone 2.
Introduction 1.2.1 PROFIBUS DP and PROFIBUS PA Transmission technology The PROFIBUS PA ( PA = Process Automation) is a variant of the PROFIBUS DP (DP = Distributed Peripherals) which is widely used in manufacturing. The PROFIBUS PA makes use of special transmission technology and therefore meets the requirements of process automation and process engineering. This transmission technology is defined in the international standard IEC 1158–2.
Introduction Master Master (class 1) (class 2) PROFIBUS DP PROFIBUS PA J Slaves (field devices, distributed I/Os, lower–level controls, gateway to PROFIBUS PA) Fig. 1-1 Typical PROFIBUS automation system Fig. 1-1 shows a section of a typical PROFIBUS automation system. The control system consists of two masters with distributed tasks: The master class 1 performs open–loop and closed–loop control tasks, master class 2 is used for HMI functions.
Introduction Profiles In addition to the EN standard 50170, the PNO (PROFIBUS user organization) has defined the functionality of the individual field device types in a profile description. These profiles define minimum functional requirements and optional extensions. The device–internal ”device management” provides the configuration tool of the control system with all basic information necessary to locate the profile parameters.
Introduction The maximum number of devices that you can connect to a bus train depends on the current consumption and the application conditions. During operation in a safe zone, the couplers or links supply up to 400 mA to the bus. In zones subject to explosion hazard, intrinsic safety is only ensured if the maximum power fed into the bus does not exceed certain voltage and current values.
Introduction 1 4 2 3 5 1 2 3 4 5 Fig.
Introduction 1 3 2 1 2 3 Fig.
Design and Method of Operation Design and Method of Operation 2 This Section describes the mechanical and electrical design, the components of the instrument and the principal method of operation of the instrument. 2.1 Overview Introduction The SIPART PS2 electropneumatic positioner forms a closed-loop control system together with an actuator. The current position of the actuator is acquired via a servo-potentiometer and returned as actual value x.
Design and Method of Operation The actuator position can be output as 2–wire signal Jy = 4 to 20 mA using the Jy option module. The actuator can also be monitored for two programmable limit values. Limit value alarms are output via the alarm option module that can also monitor and signal the function of the positioner and the actuator. In automatic operation the system deviation is monitored as a function of the actuating time.
Design and Method of Operation 3 11 90° 138 3 7 9 10 8 33° 10 9 8 238 7 6 5 6.1 6.2 2 1 4 1 2 3 4 5 6 6.1 6.2 7 8 9 10 11 **) Fig.
Design and Method of Operation 2.2.3 Pneumatic connections The pneumatic connections (G1/4) are located on the right-hand side of the positioner (Fig. 2-3). Positioning pressure Y1 for single and double–acting actuators Feedback shaft Inlet air PZ Positioning pressure Y2 for double–acting actuators Outlet air E with silencer on the underside of the instrument Fig.
Design and Method of Operation Positioning pressure Connection Actuator type Y1 Closed Safety position after auxiliary power failure electrical pneumatic Closed Closed Open Open Open Y1 Closed On rotary actuators the counter–clockwise direction of rotation – looking at the actuating shaft of the valve – is defined as “open”.
Design and Method of Operation 2.2.4 Mounting kit The positioner can be mounted on nearly all common types of actuators using the appropriate mounting kit. 2.2.5 Purging air switchover The purging air changeover switch above the pneumatic terminal block (Fig. 2-5) on the valve manifold can be accessed when the housing is open. When the switch is in position IN the interior of the housing is purged with very small quantities of clean and dry instrument air.
Design and Method of Operation 2.3 Method of operation The electropneumatic positioner SIPART PS together with the pneumatic actuator forms a control loop in which the actual value x is the position of the actuator rod on linear actuators and the position of the actuator shaft on rotary actuators and the reference variable w is the actuating current of a controller or manual control station of between 0/4 and 20 mA. With devices with PROFIBUS PA, the command variable w is set digitally via a bus system.
Design and Method of Operation 1 2 EH+ 3 EH– 4 J + Basic instrument 21 22 1.5 kΩ 9.2 V BE2 11 # 12 EH– 5 HART module 32 A w D Jw– Jw– 7 40 Ω 9 10 BE1 3V 41 42 3V 51 A1 Setpoint 8 BE1 31 3V Jw+ 6 A2 52 # BE1 Actual value A x=y D Positioning increments 3V Alarm module 3V 24V 24V "dy y D 61 U A U J 62 Jy module Piezoelectric pre–control 3/3 way valve Y1 Outlet air E Y1 138 PZ 8 Inlet air manometer block Positioning pressure Y1 up down Option Fig.
Design and Method of Operation Basic instrument Bus coupling 21 22 3 Bus interface w Setpoint 7 BE2 11 # 12 31 3V 32 3V 41 42 3V 51 A1 A2 BE1 9 52 # BE1 BE1 10 Actual value A x=y D Positioning increments 3V Alarm module 3V 24V 24V "dy y D 61 U A U J 62 Jy module Piezoelectric pre–control 3/3 way valve Y1 Outlet air E Y1 138 PZ 8 Inlet air manometer block Positioning pressure Y1 up down Option Fig.
Design and Method of Operation Basic instrument 1 2 EH+ 3 21 22 1.5 kΩ 9.
Design and Method of Operation Basic instrument Bus coupling 21 22 3 Bus interface w Setpoint 7 BE2 11 # # 12 31 3V 32 41 A1 3V 42 51 A2 3V BE1 BE1 9 52 # BE1 10 Actual value x=y A D Positioning increments 3V Alarm module 3V 24V 24V y "dy D U A U J Jy module 61 62 Piezoelectic pre–control Outlet air E 4/3 way valve Y2 Y2 238 Positioning pressure Y1 Y1 PZ 8 Y1 138 Inlet air manometer block Positioning up pressure Y2 down Fig.
Design and Method of Operation Bus interface MC 1 Fig. 2-11 3 4 5 6 Block diagram of the bus coupling unit, devices with PROFIBUS PA Devices with PROFIBUS PA 2.4 2 1. The EMC filter prevents malfunctions due to electromagnetic interference. 2. The reverse polarity protection permits connection of the bus cables in any way and makes installation errors almost impossible. 3. The electronic protection ensures that no impermissibly high current flows in the event of a fault.
Design and Method of Operation Opening the instrument To open the instrument you must first remove the 4 screws of the housing cover using a cross-head screwdriver. Disconnect the power supply cables. Remove the module cover (1). To do this you must first remove the 2 screws (9) with a screwdriver. ☞ Note To prevent premature wear to the fixture by the self–tapping screws (1.1) we recommend the following procedure for mounting the module cover (1): 1.
Design and Method of Operation 1.1 1 6 1.1 5 2 7 4 3 8 9 1 Module cover 1.1 Fixing screws 2 HART module 3 Jy module with ribbon cable (6) 4 Alarm module with ribbon cable (5) 7 Plug–in jumper 8 Adjustment wheel for slipping clutch 9 Transmission ratio selector Fig.
Design and Method of Operation 1.1 1 6 5 1.1 2 4 3 8 9 1 Module cover 1.1 Fixing screws 2 PA unit 3 Jy module with ribbon cable (6) 4 Alarm module with ribbon cable (5) 8 Adjustment wheel for slipping clutch 9 Transmission ratio selector Fig.
Design and Method of Operation 2.5.1 HART module (devices without PROFIBUS PA only) The HART interface is used for communication between the instrument and a HART communicator or a PC or notebook.
Design and Method of Operation 1 *) 2 3 250 Ω 4 1.5 kΩ 9.2 V 5 J HART module 6 40 Ω 7 8 9 10 BE1 HART Communicator HART modem PC / laptop *) Only required if the power source is not HART–capable. SIPROM PS2 Fig.
Design and Method of Operation 2.5.2 Alarm module Function The alarm module contains ❑ 3 binary outputs and ❑ 1 binary input The binary outputs are used to output fault signals and alarms. Configuration is described in Section 4.4 parameters 30 to 35. An external signal at the binary input (BE2) can cause the actuator either to be blocked or put in its final position, depending on the configuration.
Design and Method of Operation 2.5.4 Accessories Y1 Y1 PZ PZ Y2 Fig. 2-15 Manometer block (left for single-acting, right for double-acting actuators) Manometer block The manometer block for single-acting actuators contains two manometers that are screwed to the lateral pneumatic connection of the positioner using O–rings. The values for input pressure (inlet air PZ) and output pressure (positioning pressure Y1) are displayed.
Design and Method of Operation 2-20 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Preparing for Operation Preparing for Operation 3 This Section describes all preparations that are required before the instrument can be opened. 3.1 Instrument identification (type code) You will find the order number of the instrument on the rating plate (located on the bottom of the instrument) and on the packaging. Compare this number with the order number in Section 7.1.
Preparing for Operation 3.2 Dimension drawings 60 29,5 29,5 72 Y1 7 37 95 33 9 deep M8, 9 deep PZ Y2 29 E 48 Y1 2 80 65 50 x 4 x M6 23 All pneumatic connections G 1/4 58 96.6 13.5 182 8 11,2 Pg 13.5 h9 15 1 7 14.5 38.5 88.5 Fig. 3-2 Dimension drawing of plastic housing version 6DR4x00–xx 90 79.5 50 20.5 9.5 14 3x G1/4 9 12 25 2xM6 29.5 58.75 82 M4 Thread depth 5.5 5 3.5 5 10 5,3 9,5 Fig.
Preparing for Operation 12 6.5 29.5 59 14 29.5 27.5 29 84 E 34.5 7 Y1 2 65 50 x 4 x M6 9 deep M8, 9 deep PZ 23 All pneumatic connections G 1/4 58 96.6 13.5 182 8 Y1 11.2 Pg 13.5 h9 7 15 1 14.5 38.5 88.5 Fig. 3-4 3.3 Dimension drawing of metal housing version 6DR4x01–xx Assembly General ! Warning It is essential that you observe the following sequence during assembly to avoid injuries or mechanical damage to the positioner/extension kit: 1.
Preparing for Operation 3.3.1 Mounting kit “Linear Actuator” 6DR4004–8V The following are included in the supply of the mounting kit “Linear actuator IEC 534 (3 to 35 mm)” (see Fig. 3-5 for item Nos.): Item No.
Preparing for Operation 8. Fit the mounting bracket (1) with two hexagon head screws (9), spring washer (10) and U-washer (11) on the rear of the positioner. 9. Selection of the row of holes depends on the width of the actuator yoke. The roll (5) should engage in the pick-up bracket (2) as close to the spindle as possible, but must not touch the clamping assembly. 10.Hold the positioner with the mounting bracket on the actuator such that the pin (4) is guided within the pick-up bracket (2). 11.
Preparing for Operation 17 2 16 12 16 19 18 6 17 12 14 22 3 13 1) 2) 10 45 11 9 1 11 3) 9 10 11 1 8 10 8 11 10 Mounting on yoke with plane surface Mounting on yoke with ledge 11 10 Mounting on yoke with columns 7 21 4) As required Fig.
Preparing for Operation 3.3.3 Mounting kit “Rotary Actuator” 6DR4004–8D The following are included in the supply of the mounting kit “Rotary actuator” (see Fig. 3-6 for item Nos.): Item No. 2 3 4 4.1 4.
Preparing for Operation 4.2 15 9 14 2 18 9 1) 2) 16 17 3 3) 2 4.1 2 0%20 40 60 80 100% 3 4) Fig.
Preparing for Operation SECTION Positioner 2 3 4 4.1 4.2 9 10 14 15 16 17 18 Clutch wheel Driver Multiple-purpose plate Scale Pointer mark VDI/VDE 3845 mounting bracket Feedback shaft Hexagon-head screw M6 x 12 Retaining washer S6 Round-head screw M6 x 12 Washer Socket-head cap screw Rotary actuator Fig.
Preparing for Operation 3.4 Electrical connection ☞ Note If you require optional modules, you must install them before making any electrical connections (see Section 2.5). 3.4.1 Connections variations not ex-proof (devices without PROFIBUS PA) The electrical connections of the instrument can be made in the following ways: 2-wire connection 1 JH+ EH– 5 JW+ 6 JW– Fig. 3-8 3 4 iy = 4 ... 20 mA J 2 1.5 kΩ 9.
Preparing for Operation 3/4-wire connection + UH+ UH = 18 ... 35 V U Never jumper terminals 1–2! 1 2 3 – EH– + JW+ 4 1.5 kΩ J H= 9.2 V UH[V] – 9.2 V 1.5 kΩ 5 x) 0/4 ... 20 mA J – JW– 6 8 9 10 Fig.
Preparing for Operation Split range L+ 1 18...35 V UH+ e.g. SIPART DR21 2 3 1,5 kW 4 EH– iy Jw+ 0/4 to 20 mA Instrument 1 6 40 W 7 Jw– Positioning range 1 8 9 Total positioning range 9,2 V 5 10 BE1 M UH+ 1 2 3 4 EH– 1,5 kW 9,2 V 5 Instrument 2 Jw+ Jw– 6 7 9 10 Fig. 3-10 3-12 40 W Positioning range 2 8 BE1 Series connection of 2 positioners, e.g.
Preparing for Operation 3.4.2 Connection variants not protected from explosion hazard (devices with PROFIBUS PA) ! Warning The applicable regulations for electrical installation must be observed, in particular, in zones subject to explosion hazard ❑ the regulation about electrical equipment in zones subject to explosion hazard. The erection guidelines of the country in question must be observed.
Preparing for Operation 3. Insert the prepared bus cable through the cable gland. 4. Fix the shield to the housing with the clip and the two screws. 5. Screw the cable gland tight. 6. Connect the red and green conductors as shown in Fig. 3-12 to terminals 3 and 7 of the basic PCB. (The polarity is irrelevant.) 10 5 80 Bus cable 6XV1 830–5AH10 or 6XV1 830–5BH10 Fig.
Preparing for Operation The specified noise immunity and noise emission are only ensured if the bus shield is fully effective. This includes connecting the shields with the metallic connections of the SIPART PS2 with PROFIBUS PA, but also routing the shields to the terminal boxes, distributors, DP/PA coupler or DP/PA link. Suitable equipotential bonding must be provided to avoid potential differences between the individual sections of the plant and therefore the associated hazards or function impairment.
Preparing for Operation Binary outputs L+ 1kΩ A2 A1 51 41 31 52 42 32 + 35 V e. g. SIPART DR21 24 V BE – 5V Fig. 3-14 Alarm module 6DR4004–8A Binary input BE2 21 +3V 22 +13 V w1 BE2 # 11 12 +4.5 V Fig.
Preparing for Operation 3.4.4 Connection variations ex-proof (devices with PROFIBUS PA) ☞ Note Only certified, intrinsically safe electric circuits must be connected as auxiliary power, control and signal current circuits. Non-hazardous area Hazardous area zone 1 or zone 2 1 + JH+ 2 3 iy = 4 ... 20 mA 4 EH– 1.5 kΩ 9.2 V 5 EEx – JW+ JW– 6 8 9 10 Fig.
Preparing for Operation 3.4.5 Connection variations ex-proof (devices with PROFIBUS PA) not potentially explosive atmosphere potentially explosive atmosphere zone 1 9 ... 24 V + # 3 PROFIBUS PA 7 – A Positioner EEx 9 DP/PA coupling +3V 10 # binary input 1 Fig. 3-17 Electric connection of basic device with PROFIBUS PA (6DR410x–xE) 3.4.
Preparing for Operation Binary outputs Hazardous area zone 1 or zone 2 2.1 kΩ 10 kΩ Fig. 3-19 A2 A1 51 41 31 52 42 32 Non-hazardous area EEx + DIN DIN 19234 switching amplifier – Binary outputs alarm module 6DR4004–6A Binary input BE2 Hazardous area zone 1 or zone 2 Non-hazardous area 21 3V 22 = w1 BE2 # = 11 12 EEx Fig.
Preparing for Operation 3.5 Pneumatic connection ! ☞ Warning For safety reasons the pneumatic power must only be input after installation when the positioner is switched to operating level P manual mode with the electrical signal applied (state of supply, see Fig. 4-2). Note Check the air quality! Industrial air, free of oil, solid content < 30 mm, dew point under pressure 20 K below the lowest ambient temperature.
Preparing for Operation 3.6 Commissioning After you have mounted the positioner on the actuator and connected the power supply and established the pneumatic connection you must initialize the positioner. Before it is initialized the positioner is in P manual mode (that can also be set with 36.PRST) – “NO INIT” blinks. ☞ Note To prepare for initialization please perform the steps described in the Assembly and Installation Instructions Section 7.
Preparing for Operation Initialization Initialization is largely automatic. Linear actuator up Fig. 3-21 Rotary actuator Closed down Open Actuation direction of actuators The initialization procedure is shown in the following flowchart (Figs. 3-22 to 3-24). Configuring >5s Traverse the working range of the actuator with 1 RUN 1 Potentiometer value normalized manipulated variable [%] Continue using: Inlet valve 1 max. 30 s open no ∆y > 10 % ? Outlet valve or inlet valve 2 max.
Preparing for Operation 2 continue using: Set Lever into horizontal position using Potentiometer value normalized manipulated variable [%] Actuator in down position (Hart position) Check down tolerance band 4 % to 20 % Not for rotary actuators 1) continue using: no Clutch operated ? continue using: 1) yes For rotary actuators: 4 to 10 % Correct height adjustment or turn clutch until appears in the lower display 4 > d > 20 % ? no yes RUN 2 Actuator in up 2) direction (Hart position or set value
Preparing for Operation 3 Actuator down 1) direction ascertain pulse-stop time up down continue using: Set restrictors to prolonged actuating time s. Section 2.2.6 RUN 3 Actuator up 2) direction ascertain pulse-stop time down up Actuating time [s] too small Actuator stops Actuating times > 1.5 s ? no yes blinks Actuating time [s] If short actuating time desired altern.
Operation 4 Operation This Section describes operation of the positioner. 4.1 Display The LC display has two lines of text. Each line is segmented differently; the elements of the upper line consist of 7 and those of the lower line of 14 segments. The display depends on the mode selected (see Section 4.3). ☞ Note If the positioner is operated in zones with temperatures below –10 °C, the liquid crystal display becomes slow and the refresh rate of the display slows down considerably. 4.
Operation 4.3 Modes Display Mode Position [%] Automatic Setpoint [%] 1x >5s Position [%] Manual Setpoint [%] Change position with >5s Preset Parameter value Parameter number and parameter name >5s Potentiometer setting [%] Not initialized (obtained with Preset) Fig. 4-2 Configure xx.xxxx P manual operation Change position with Changing mode Automatic mode (AUT) Automatic mode is the normal mode.
Operation Configuring With the mode button you can switch from automatic or manual mode to “Configuring” mode (see Fig. 4-2). To do this press the button for at least 5 seconds until switchover has been completed. In “Configuring” mode you can change the parameter values of the positioner. The upper line of the display shows the current parameter value, the lower the parameter name (in abbreviated form) and the parameter number. You can select the next parameter with the mode button.
Parameter name Display Function turn (part-turn actuator) Type of actuator 1.YFCT Unit Parameter values Factory setting WAY WAY (linear actuator) LWAY (linear actuator without sine correction) 2.YAGL 1) Rated angle of rotation of feedback 90° Set transmission ratio selector (7) appropriately 33° Degrees 33° mm oFF (see view of device) 3.
Operation 1.YFCT Type of actuator Selection of the actuator used: linear actuator (WAY), rotary actuator (turn). The non-linearity that occurs on linear drives due to the transmission of the linear to rotary motion is compensated for by the positioner, if 1.YFCT = WAY is selected. If an external linear potentiometer is used for position acquisition for linear actuators, 1.YFCT must be set to LWAY. After initialization, the position is not displayed.
Operation ☞ Note The setting for YWAY must correspond to the mechanical leverage ratio. The driver must be set to the value of the actuator travel or, if this value is not scaled, to the next largest scaled value. 4.INIT Initialization Automatic initialization is started when you select “Strt” and press the increment key (> 5 s). Initialization is displayed by “RUN 1” to “RUN 5” (see Fig. 3-22 to Fig. 3-24) as it progresses. 5.
Operation y=x 100 % Instrument 1 6.SDIR = FALL Total positioning range Instrument 2 6.SDIR = riSE 0% 100 %–SPRE 100 %–SPRA SPRA Instrument 1 Positioning range 1 Fig. 4-5 9.TS SPRE Instrument 2 Positioning range 2 100 % JW [0 % to 100 %] Example: split-range operation with two instruments Setpoint ramp The setpoint ramp takes effect in automatic mode and limits the rate of change of the active setpoint.
Operation 11.SL0 to 21.SL10 Setpoint turning points (see Fig. 4-6) Each setpoint turning point can be assigned a flow characteristic value at intervals of 10%. These points produce a polygon consisting of 10 straight lines which results in an image of the valve characteristic curve. Setpoint turning points can only be entered when 10.SFCT = FrEE. 25.YNRM = 25.YNRM = MPoS FLoW [%] [%] 100 YE = 96 % only if 26.YCLS = uP 98.5 % 99.5 % 100 90 10.SFCT = FrEE e.g. 1:25 inverse 90 80 70 60 80 70 60 10.
Operation 22.DEBA Dead zone of the controller when DEBA = AUto the dead zone is constantly adapted to the requirements of the control loop in automatic mode. If control oscillation is detected the dead band is increased step by step. Reverse adaptation is achieved using a time criterion. In other discrete settings the permanent value for the dead zone is used. 23.YA Start of manipulated variable limiting (see Fig. 4-6 and Fig. 4-7 ) and 24.YE End of manipulated variable limiting (see Fig. 4-6 and Fig.
Operation YNRM = MPOS or YNRM = FLOW Default: YA = 0% and YE = 100% 50% 4mA 7.2mA 0% 20% 0mm 16mm 10.4mA 13.6mA 60% 40% 32mm 48mm 16.8mA 80% 64mm 20mA 100% 80mm YA = 0% Input current (Setpoint) X display W display Mechan. travel (readback) YE = 100% Example: YNRM = MPOS with YA = 10 % and YE = 80 % 50% 4mA 0% 0mm 7.2mA 10.4mA 20% 40% 16mm 13.6mA 60% 32mm 16.8mA 80% 48mm YA = 10% 64mm 20mA Input current (Setpoint) X display 100% W display 80mm Mechan.
Operation 27.YDIR Direction of manipulated variable for display Used to set the direction of action (rising or falling) for the display and position feedback (Jy). 28.BIN1 Function Binary input 1 (see Fig. 4-4) and 29.BIN2 Function Binary input 2 (see Fig. 4-4) Parameters 28.BIN1 and 29.BIN2 can be set individually to suit the task: ❑ BIN1 or BIN2 = on or –on Binary signals from peripheral devices (e.g.
Operation 31.A1 Response threshold of alarm 1 and 32.A2 Response threshold of alarm 2 The response thresholds refer to the mechanical path (MPOS scale). Function of alarm output on fault 33. FCT The fault alarm for monitoring the system deviation over time can also be triggered by the following events: ❑ Loss of power ❑ Process fault ❑ Actuator fault ❑ Valve fault ❑ Loss of pressure The alarm fault can also be logically ORed with the non–automatic signal (Manual or Configuring) and the binary inputs.
Parameter name Display Function turn (part-turn actuator) Type of actuator 1.YFCT Unit Parameter values Factory setting WAY WAY (linear actuator) LWAY (linear actuator without sine correction) 2.YAGL 1) Rated angle of rotation of feedback 90° Set transmission ratio selector (7) appropriately 33° Degrees 33° mm oFF (see view of device) 3.
Operation 1.YFCT Type of actuator Selection of the actuator used: linear actuator (WAY), rotary actuator (turn). The non-linearity that occurs on linear drives due to the transmission of the linear to rotary motion is compensated for by the positioner, if 1.YFCT = WAY is selected. If an external linear potentiometer is used for position acquisition for linear actuators, 1.YFCT must be set to LWAY. After initialization, the position is not displayed.
Operation ☞ Note The setting for YWAY must correspond to the mechanical leverage ratio. The driver must be set to the value of the actuator travel or, if this value is not scaled, to the next largest scaled value. 4.INIT Initialization Automatic initialization is started when you select “Strt” and press the increment key (> 5 s). Initialization is displayed by “RUN 1” to “RUN 5” (see Fig. 3-22 to Fig. 3-24) as it progresses. 5.SDIR Setpoint direction (see Fig.
Operation 09.SL0 to 29.SL20 Setpoint turning points (see Fig. 4-9) Each setpoint turning point can be assigned a flow characteristic value at intervals of 5%. These points produce a polygon consisting of 20 straight lines which results in an image of the valve characteristic curve. Setpoint turning points can only be entered when 8.SFCT = FrEE. 33.YNRM = 33.YNRM = MPoS FLoW [%] [%] 100 YE = 96 % 100 90 8. SFCT = n1:25 90 80 70 60 80 70 60 8.SFCT = lin 50 50 40 8.
Operation 30.DEBA Dead zone of the controller when DEBA = AUto the dead zone is constantly adapted to the requirements of the control loop in automatic mode. If control oscillation is detected the dead band is increased step by step. Reverse adaptation is achieved using a time criterion. In other discrete settings the permanent value for the dead zone is used. 31.YA Start of manipulated variable limiting (see Fig. 4-8) and 32.YE End of manipulated variable limiting (see Fig. 4-8) With parameters 31.
Operation YNRM = MPOS or YNRM = FLOW Default: YA = 0% and YE = 100% 50% 4mA 7.2mA 0% 20% 0mm 16mm 10.4mA 13.6mA 60% 40% 32mm 48mm 16.8mA 80% 64mm 20mA 100% 80mm YA = 0% Input current (Setpoint) X display W display Mechan. travel (readback) YE = 100% Example: YNRM = MPOS with YA = 10 % and YE = 80 % 50% 4mA 0% 0mm 7.2mA 10.4mA 20% 40% 16mm 13.6mA 60% 32mm 16.8mA 80% 48mm YA = 10% 64mm 20mA Input current (Setpoint) X display 100% W display 80mm Mechan.
Operation 37 37.BIN1 Function Binary input 1 (see Fig. 4-8) and 38.BIN2 Function Binary input 2 (see Fig. 4-8) Parameters 28.BIN1 and 29.BIN2 can be set individually to suit the task: ❑ BIN1 or BIN2 = on or –on Binary signals from peripheral devices (e.g. pressure or temperature switches) can be read out via the HART interface or trigger the alarm output if logically ORed with other signals. ❑ BIN1 = bLc1 Operating level Configuring is disabled so that it cannot be reset (e.g.
Operation 42. FCT Function of alarm output on fault The fault alarm for monitoring the system deviation over time can also be triggered by the following events: ❑ Loss of power ❑ Process fault ❑ Actuator fault ❑ Valve fault ❑ Loss of pressure The alarm fault can also be logically ORed with the non–automatic signal (Manual or Configuring) and the binary inputs. 43.
Operation 46.FSTY Safety position This parameter is used to move the actuator into a set safety position if communication fails. Three settings are possible ❑ FSVl the actuator must continue to control with the parameterized safety setpoint ❑ FSSP the actuator must continue to control with the last effective setpoint ❑ FSAC Here this outlet air valve is opened and the single–action actuator moves to its final position by spring power. 47.
Operation 4.
Operation PC or PG (Master class 2) Power supply PROFIBUS DP Bus termination PROFIBUS PA MPI cable (is required for commissioning and monitoring) DP/PA Coupler DP/PA Link Splitters CPU SIMATIC S7 (Master class 1) PA devices Fig. 4-11 Example of a small PROFIBUS DP/PA system Here is a small STEP 7 program that establishes cyclic data transmission with the SIPART PS2 PA. Fig.
Operation In this example, all files supported by the device are transmitted in the input or output direction. 256 (W#16#100) is selected as the initial I/O address. Legend Byte 15 Byte 15 15 bytes of input data consisting of the following: READBACK 5 bytes RCAS_OUT 5 bytes CHECKBACK 3 bytes POS_D 2 bytes Byte 10 10 bytes of output data consisting of the following: SP 5 bytes RCAS_IN 5 bytes (see Object table in the Appendix) 4.5.
Operation Position discrete The discrete position of the valve is displayed as a value (1 byte) with the following meaning: 0 = not initialized 1 = valve closed 2 = valve open 3 = valve in intermediate state There is a status for this value too (1 byte) Checkback The checkback is displayed bit–coded in 3 bytes: Byte Bit Meaning for ”1” 0 0 Device in failsafe position 1 Request for local operation 2 Device is operated locally 3 Emergency operation active 4 Deviation of the motion direction
Operation Remote cascade output This output provides the current setpoint in AUTO mode and remote cascade. The status is used especially for the transition from AUTO to remote cascade. In conjunction with the parameter input variable (primary value scale) you cannot only set the setpoints to the SIPART PS2 PA positioner as a percentage of the valve position but also in physical quantities such as cubic meters per day or liters per minute. It is also possible to adapt the readback values to this scaling.
Operation 1 1 0 0 0 1 s. a. good (cascade), initialization confirmed 1 1 0 0 1 0 s. a. good (cascade), initialization requested 1 1 0 0 1 1 s. a. good (cascade), not requested 1 1 0 1 1 0 s. a. good (cascade), local operation has priority 1 1 0 1 1 1 s. a. good (cascade), device is in failsafe position 1 1 1 0 0 0 s. a.
Operation READBACK, POS_D, SP Readback, position discrete, setpoint Input (master view) Initial address 0 1 READBACK – 2 floating–point number 3 4 READBACK – status 5 POS_D 6 POS_D – status Output (master view) Initial address 0 1 SP – 2 floating–point number 3 4 Checkback, SP SP – status Checkback, setpoint Input (master view) Initial address 0 1 CHECKBACK 2 Output (master view) Initial address 0 1 SP – 2 floating–point number 3 4 4-28 SP – status Positioner SIPART PS2/SIPAR
Operation READBACK, CHECKBACK, POS_D, SP Readback, position discrete, checkback, setpoint Input (master view) Initial address 0 1 READBACK – 2 floating–point number 3 4 READBACK – status 5 POS_D 6 POS_D – Status 7 8 CHECKBACK 9 Output (master view) Initial address 0 1 SP – 2 floating–point number 3 4 RCAS_OUT, CHECKBACK, RCAS_IN SP – status Remote cascade output, checkback, remote cascade input Input (master view) Initial address 0 1 RCAS_OUT – 2 floating–point number 3 4 RCAS_
Operation READBACK, RCAS_OUT, POS_D, CHECKBACK, SP, RCAS_IN Readback, remote cascade output, position discrete, checkback, setpoint, remote cascade input Input (master view) Initial address 0 1 READBACK – 2 floating–point number 3 4 READBACK – status 5 6 RCAS_OUT – 7 floating–point number 8 9 RCAS_OUT – Status 10 POS_D 11 POS_D – Status 12 13 CHECKBACK 14 Output (master view) Initial address 0 1 SP – 2 floating–point number 3 4 SP – status 5 6 RCAS_IN – 7 floating–point number
Operation 4.5.2 Diagnostics acc. to PROFIBUS DP (DDLM_Slave_Diag) The SIPART PS2 PA positioner provides diagnostic data in the following form: Input (master view) Initial address 0 Station_status_1 1 Station_status_2 2 Station_status_3 3 Diag_Master_Add 4 Ident_Number 5 Ident_Number 6 Header 7 Status_Type Status coding 8 Slot_Number acc.
Operation Diagnostics Byte 0 1 4-32 Bit Meaning for ”1” 0 Electronics defective 1 Mechanics defective 2 – 3 – 4 Memory error 5 – 6 Device not initialized 7 Self–calibration failed 0 Zero–point error 1 – 2 Invalid configuration 3 – 4 – 5 – 6 Characteristic invalid 7 – 2 – 3 – Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Fig. 4-13 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01 BE2 BE1 28.BIN1 3.YWAY 2.YAGL BE2 block . Selected from the table of configuration parameters Block conf.and manual Block conf. BE1 8.SPRE to .
Operation 4-34 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Service and Maintenence Service and Maintenance 5 To a great extent the instrument requires no maintenance. However, if the valves fail due to the use of unsuitable compressed air, they can be replaced. Please contact your local Siemens office. ! Danger Avoid electrostatic charges in zones subject to explosion hazard. Electrostatic charges can be caused when the instrument is cleaned with a dry cloth.
Service and Maintenance 5-2 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Technical Data 6 Technical Data General data: basic instrument 6DR400x–xx (without PROFIBUS PA) and 6DR410x–xx (with PROFIBUS PA) Climatic category IEC 721 Storage 1K5 but – 40 °C to + 80 °C 1) Transport 2K4 but – 40 °C to + 80 °C 1) Operation without purging air 3K3 but – 30 °C 3) to + 80 °C 2) 3K4 but – 30 °C 3) to + 80 °C 2) with purging air Degree of protection IP65 acc. to EN60529 Dimensions plastic housing see Fig. 3-2 metal housing see Fig.
Technical Data General data: basic instrument 6DR400x–xx and 6DR410x–xx AD converter Sampling time 12.5 ms Resolution v 0.05 % Transmission error v 0.2 % Temperature influence v 0.1 % / 10 K Controller data 5–step switch Dead zone adaptive dEbA = Auto adaptive or dEbA = 0.1 to 10 % fixed setting Controllable actuating times w 1.
Technical Data Electrical data: basic instrument without PROFIBUS PA 6DR4000–1N/–2N and 6DR4001–1N 6DR4000–1E/–2E and 6DR4001–1E Degree of protection acc. to EN 50014 and EN 50020 – II2G EEx ib II C T4/T5/T6 Place of installation – zone 1 + 2 – 30 to + 80 °C Ambient temperature T4 – 30 to + 80 °C T5 – 30 to + 65 °C T6 – 30 to + 50 °C 2-wire circuit Fig. 3-8 Fig. 3-16 Nominal signal range 4 to 20 mA Current for maintenance of power supply w 3.6 mA UB w 10 V without HART module UB w 11.
Technical Data 6DR4000–1N/–2N and 6DR4001–1N 6DR4000–1E/–2E and 6DR4001–1E Current input iw Nominal signal range 0 or 4 to 20 mA v 0.85 V without HART module v 2.4 V with HART module Load voltage at 20 mA Static destruction limit " 40 mA – Internal capacitance Ci – 19 nF Internal inductance Li – 0.
Technical Data Electrical data: basic instrument with PROFIBUS PA 6DR4100–1N 6DR4100–2N 6DR4101–1N 6DR4100–1E 6DR4100–2E 6DR4101–1E Degree of protection acc. to EN 50014 and EN 50020 EEx ia IIC T4/T5/T6 Ambient temperature T4 –30 to +80 °C T5 –30 to +65 °C T6 –30 to +50 °C Place of installation zone 1 Power supply Bus voltage conducted on bus 9 to 32 V 9 to 24 V 12 mA " 10 % Power consumption Imax = v 16 mA in case of fault Electronic current limitation Effective internal inductance Li v 7.
Technical Data Electrical data: options 6DR4004–8x 6DR4004–6x Acc. to EN 50014 and EN 50020 – II2G EEx ib II C T4/T5/T6 2) Place of installation – zone 1 Ambient temperature – 30 to + 80 °C T4 – 30 to + 80 °C T5 – 30 to + 65 °C T6 – 30 to + 50 °C Alarm module 6DR4004–8A 6DR4004–6A +3% conductive R = 1 kΩ –1% w 2.1 mA 1) Binary outputs, A1, A2, Signal state High (not available) Signal state Low (available) 3) blocked IR < 60 µA v 1.2 mA 1) Internal capacitance Ci – 4.
Technical Data Jy module 6DR4004–8J 6DR4004–6J 2-wire circuit Nominal signal range i 4 to 20 mA short circuit proof Control range Power supply 3.6 to 20.5 mA UH + 12 to 35 V + 12 to 30 V External load RB [kΩ ] v (UH [V] – 12 V) / i [mA] Transfer error v 0.3 % v 0.1 % / 10 K Effect of temperature v 0.1 % Resolution v1% Residual ripple Internal capacitance Ci – v10 nF Internal inductance Li – 0.2 mH – v 30 V Ji – v 100 mA Pi – v1W to the basic instrument Jy (Kl.
Technical Data 6-8 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Supply Range 7 Supply Range The positioner and its option modules are supplied as separate units and in different versions. Positioners and option modules are available for operation in zones with and without an explosion hazard. These versions are marked by a special rating plate. ! 7.1 Warning When combining components, make sure that only positioners and option modules can be combined that are approved for the zone where they will be used.
Supply Range 7.2 Supply range of options Option Order number HART module not ex-proof (devices without PROFIBUS PA only) 6DR4004–8H HART module exi (devices without PROFIBUS PA only) 6DR4004–6H Alarm module not ex-proof 6DR4004–8A Alarm module exi (PTB) Alarm module exi (FM) 6DR4004–6A 6DR4004–7A Jy module not ex-proof (PTB) 6DR4004–8J Jy module exi Jy module exi (FM) 6DR4004–6J 6DR4004–7J 7.
A Appendix A1 Index Accessories, 2-14 Alarm function, 4-10 Alarm module, 2-13 Automatic mode, 4-2 Initialization, 3-18, 4-6 Jy module, 2-13, 3-12 Binary input, 3-13, 3-15 Binary outputs, 3-13, 3-15 Leverage ratio, 4-6 Linear actuator, 1-3 Commissioning, 3-17 Configuring, 4-3 Control pushbuttons, 4-1 Current output, 3-14 Dimension drawing, 3-2 Dimension drawings, 3-2 Display, 4-1 Double acting, 1-4 Electrical connection, 2-2, 3-10 not ex-proof, 3-10 Electronic connection, ex-proof, 3-14
Appendix Restrictors, 2-5 Rotary actuator, 1-4, 3-9 Service, 5-1 Setpoint characteristics, 4-8 Single acting, 1-3 Split range, 3-12 Standards, 0-5 Supply range, 7-1 A-2 Technical data, 6-1 Use as intended, 0-4 Warning notes, 0-2 Warranty information, 0-4 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
A2 Device master data file (GSD) Device master data file of the SIPART PS2/PS positioner: The device master data file (GSD) is necessary to be able to communicate with the SIPART PS2 PA positioner. It essentially describes the data formats supported. This file will soon be available in the Internet: Homepage: www.ad.siemens.de, click on Support, click on Simatic, search for GSD The following pages show a printout of the GSD See following pages for an example.
;********************************************************** ;** GSD Datei fuer SIPART PS 2 PA, SIEMENS AG ** ;** MLFB: 6DR410x–xx ** ;** Stand: 30.10.98 ** ;** Datei: SIS18079.GSD ** ;********************************************************** ; #Profibus_DP GSD_Revision = 1 Vendor_Name = ”SIEMENS AG” Model_Name = ”SIPART PS 2” Revision = ”V1.0” Ident_Number = 0x8079 Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = ”A01” Software_Release = ”Z01” 31.25_supp = 1 45.45_supp = 1 93.
User_Prm_Data_Len User_Prm_Data = 3 = 0x00,0x00,0x00 ;Modules for Analog Output ; ; RB = READBACK, CB = CHECKBACK, RC_OUT = RCAS_OUT, RC_IN = RCAS_IN ; Module = ”SP ” 0xA4 EndModule Module = ”RC_OUT, RC_IN ” 0xB4 EndModule Module = ”READBACK + POS_D, SP ” 0x96, 0xA4 EndModule Module = ”CHECKBACK, SP ” 0x92, 0xA4 EndModule Module = ”READBACK+CHECKBACK+POS_D, SP ” 0x99, 0xA4 EndModule Module = ”RC_OUT + CHECKBACK, RC_IN ” 0x97, 0xA4 EndModule Module = ”RB+ RC_OUT+CB+ POS_D, SP+RC_IN ” 0x9E, 0xA9 EndModule ;
A3 SIMATIC object table On the following pages you will find a table of all SIMATIC object parameters of the SIPART PS2 PA.
Slot Index abs Index rel 1 0 1 Ele– ment Default Value Object Parameter Description Data Type Anzahl cyclic read write Device Management 1 1 HEADER 1 0x0000 Dir_ID Directory ID (reserved) 2 0x0001 Num_Dir_Rev Directory Revision Number 3 0x0001 Num_Dir_Obj Number of Directory Objects (Directories) 4 0x0006 Num_Dir_Entries Total Number of Directory Entries 5 0x0001 First_Comp_Dir_Entry Entry number of first Composite List Dir Entry 6 0x0003 Num_Comp_Dir_Entry Number of
4 0x0000 Disabled Parameters of the Physical Block (mandatory and optional) 22 8 23 9 24 10 25 t1 SOFTWARE_REVISION Software Revision octet_string 16 r HARDWARE_REVISION Hardware Revision octet_string 16 r DEVICE_MAN_ID Manufacturer unsigned16 1 r 11 DEVICE_ID Device identification (unique) visible_string 16 r 26 12 DEVICE_SER_NUM Device service number visible_string 16 r 27 13 0x00000000 DIAGNOSIS Detailed device info (bit–coded) octet_string 4 r 29 15 0xD05
Actuator Function Block AO (Analog Out) 1 90 0 BLOCK_OBJECT Block characteristic ds32 1 r Counter that is incremented on every change of configuration parameters unsigned16 1 r TAG_DESC Unique tag in the system that the user can specify visible_string 32 r, w 1 250 Reserved 2 0x02 Block Object Block type (function) 3 0x02 Parent Class Output 4 0x01 Class Analog output 5 0x00000000 DD–Reference (reserved) 6 0x0000 DD–Revision (reserved) 7 0x4002 Profile 8 0x0300 Pro
112 22 0x139 OUT_CHANNEL Assignment (positioning) 113 23 30 FSAVE_TIME 114 24 0 FSAVE_TYPE 115 25 0 117 27 121 unsigned16 1 r, w Response time after communication failure float 1 r, w Type of response to communication failure unsigned8 1 r, w FSAVE_VALUE Setpoint on communication failure float 1 RCAS_OUT Readback in Remote Cascade mode ds33 1 x r Position of the valve actuator ds34 1 x r 1 0 Value 2 0x4f Status 1 0 Value 2 0x4f Status 31 POS_D to t
155 4 0 ALERT_KEY Value can be written to by the user for alarm processing unsigned8 1 r, w 156 5 0x08 TARGET_MODE Target mode of the PB = Auto unsigned8 1 r, w 157 6 MODE_BLK Set block mode ds37 1 r ds42 1 r 158 1 0x08 Actual Auto 2 0x98 Permitted Auto, O/S, LO Auto 3 0x08 Normal Auto 7 ALARM_SUM 1 0x0000 2 0x0000 Unacknowledged 3 0x0000 Unreported 4 0x0000 Disabled Alarm status Current_Alarm Parameter of the Transducer Block (mandatory and optional) 160
209 58 FEEDBACK 1 0 Value 2 0x4f Status Current position ds33 1 r 221 70 0 BIN_IN_1_FUNCT Function of binary input 1 unsigned8 1 r, w 222 71 0 BIN_IN_2_FUNCT Function of binary input 2 unsigned8 1 r, w 223 72 0 ALARM_FUNCT Function of the alarm outputs unsigned8 1 r, w 224 73 10.0 ALARM_1 Alarm value 1, with ref. to OUT_SCALE float 1 r, w 225 74 90.0 ALARM_2 Alarm value 2, with ref.
A4 References and catalogs No.
A-14 Positioner SIPART PS2/SIPART PS2 PA C79000-G7476-C150–01
Siemens AG Bereich Automatisierungs- und Antriebstechnik Geschäftszweig A&D PA D-76181 Karlsruhe E